Modular Power Series
855-340-004_Rev2.0_Instruction Manual
Page
28
of 81
NOTE: A Battery Discharge Test of a fully charged battery can be manually
initiated by changing the discharge test Status parameter to
"Enabled".
3.2.3 Load Distribution Module (if installed)
The LDM Status screen shows the output current for each of the four
outputs. Use the Up/Down buttons to scroll through multiple LDM screens
(if installed).
Other information will be shown depending on the operating state of the unit:
•
OPEN will be displayed if the circuit breaker is open
•
OFF will be displayed if the output has been disabled in the Output
Control screen.
Press Enter to move to the LDM Settings.
LDM Settings
The load current level alarm can be set by adjusting the Output Overcurrent,
or Output Undercurrent threshold.
Scroll to highlight the sub-menu to change.
•
Output Control
•
Output Overcurrent
•
Output Undercurrent
Press Enter to select.
Scroll to choose Output to be changed
(On/Off control shown).
Press Enter to select.
Use the Up/Down buttons to adjust setting,
press Enter to set value and return to
previous screen. Press Back
X
to return to
previous screen without saving changes.