Modular Power Series
855-340-004_Rev2.0_Instruction Manual
Page
63
of 81
The MIB file can also be downloaded from within the GUI. There are links
in the SNMP section of the Communications Network Setup tab and on the
Help tab. The unique unit MIB file must then be imported into the external
SNMP management software.
Enable SNMP:
Select this check box to enable the SNMP agent. The
default setting is Disabled.
SNMP Version:
Set the SNMP version (v1/v2c, v3, or All) supported by
the SNMP agent. If "All" is selected, all SNMP versions will be supported
simultaneously. The appropriate settings for the selected SNMP version
will need to be configured.
Enable SNMP Write Access:
Select this check box to enable remote
SNMP control of the system output and individual LDM output channels.
If this box is unchecked, all information available from the SNMP agent
will be read-only.
SNMP Control Access
: Set the level of unit control that is allowed
through SNMP. This setting is only available if Enable SNMP Write
Access is enabled.
•
Output Control:
Allows remote SNMP control of the system output
and LDM channel outputs only.
•
Full Device Control
: Allows SNMP client to set all unit settings
through SNMP. This setting requires a different MIB file which can
be downloaded from the ICT Website: https://www.ict-
power.com/resources/tools-utilities/.