Modular Power Series
855-340-004_Rev2.0_Instruction Manual
Page
26
of 81
LOW SOC ALARM (only available for lead-acid batteries):
Set the
"Low SOC Alarm" (%) if desired, to raise an alarm when the battery is
nearly discharged. With lithium-ion batteries, this feature is built into the
BMS.
TEMP-CO/cell (only available for lead-acid batteries):
Ensure the
Battery Temperature Sensor (ICT-TMP) is installed and connected to the
battery case (see
Section 2.7) for optimal lead-acid battery charging and
best battery life. Set the "Temperature Compensation/°C” level per
battery cell to match the recommendation of the battery manufacturer
(−4 mV/°C per cell is typical).
EQUALIZE CHARGE (only available for lead-acid batteries):
WARNING
Risk of serious personal injury or damage to equipment and
property! Always observe the following:
•
Equalize charging is intended for flooded lead-acid batteries
only and may produce higher than normal levels of
hydrogen gas.
•
Do not use equalization charging with lithium-ion
batteries
.
•
Ensure the battery compartment is well ventilated to avoid
any risk of explosion.
•
Always consult with battery manufacturer and observe all
battery manufacturer recommendations.
Configure the "Battery Equalize Charge" voltage, duration, and
automatic repeat interval if desired when using flooded lead-acid type
batteries only. The system will step up the output voltage to the Equalize
Voltage for the Equalize Duration time whenever the Equalize Status is
set to Enable. The unit’s log (see Section 4.7.1) will record the
completion of the equalization charge.
Press Enter to select.
Scroll to highlight parameter in selected
sub-menu.
•
Voltage
•
Duration
•
Status (display only)