PN
Function
Range of value
De-
fault
User-
level
Analog output
22
Analog output
0 = deactivated
1 = current measurand
2 = min-value
3 = max-value
4 = Hold-value
5 = absolute value
1
4
23
Signal selection
0 = 0-10 VDC
1 = 0-20 mA
2 = 4-20 mA
2
4
25
Disturbance behaviour of the analog output
0 = run onto limit values (as before)
1 = switch to final value at
exceedance of output area
2 = switch to initial value at
exceedance of output area
(PN20/21)
3 = switch to highest value (0x0000)
at exceedance of output area
(PN20/21)
4 = switch to smallest value (0x0000)
at exceedance of output area
(PN20/21)
5 = switch to final value at converter,
over-/underflow, wire break (bars)
6 = switch to initial value at
converter, over-/underflow, wire
break (bars)
7 = switch to highest value (0xFFFF)
at converter, over-/underflow, wire
break (bars)
8 = switch to smallest value
(0xFFFF) at converter, over-
/underflow, wire break (bars)
5
4
Interface
34
Switchover of interface behaviour
0 = standard operation
1 = transmitting operation
0
4
35
Measurand that has to be transmitted
1 = current measurand
2 = min-value
3 = max-value
4 = Hold-value
5 = absolute value
1
4
30
8. Program number description