![ICS IPM5 Скачать руководство пользователя страница 34](http://html1.mh-extra.com/html/ics/ipm5/ipm5_user-manual_3538998034.webp)
PN
Function
Range of value
De-
fault
User-
level
71
Threshold
-9999…99999
1000
6
72
Hysteresis
0…99999
0
5
73
Operation type quiescent current /
operating current
0 = quiescent current
1 = operating current
1
5
74
Switching delay
0.0…10.0 seconds
0.0
5
75
Type of delay
0 = none
1 = switching-on delay
2 = switching-off delay
3 = switching-on/-off delay
0
5
Switchpoint 3
80
Switchpoint 3
0 = deactivated
1 = current measurand
2 = min-value
3 = max-value
4 = Hold-value
5 = absolute value
6 = sensor error
1
5
81
Threshold
-9999…99999
1000
6
82
Hysteresis
0…99999
0
5
83
Operation type quiescent current /
operating current
0 = quiescent current
1 = operating current
1
5
84
Switching delay
0.0…10.0 seconds
0,0
5
85
Type of delay
0 = none
1 = switching-on delay
2 = switching-off delay
3 = switching-on/-off delay
0
5
Switchpoint 4
90
Switchpoint 4
0 = deactivated
1 = current measurand
2 = min-value
3 = max-value
4 = Hold-value
5 = absolute value
6 = sensor error
1
5
91
Threshold
-9999…99999
1000
6
92
Hysteresis
0…99999
0
5
93
Operation type quiescent current /
operating current
0 = quiescent current
1 = operating current
1
5
94
Switching delay
0.0…10.0 seconds
0,0
5
32
8. Program number description