6. Operation and function description

Optical response, display flashing

The switching on of one or more setpoints can also be set to trigger a flashing of the display to

enhance the optical response.

Example:

Let us assume the threshold for flashing of the display is set at setpoint 2. If setpoint 1 is

exceeded and setpoint 2 is not, the setpoint

LED 1

lights up permanently. If setpoint 2 exceeds

the threshold, the 7-segment display will start to flash, setpoint 1 will light up permanently and

setpoint LED 2 will flash.
The flashing enhances the optical response and the operator sees immediately that an important

threshold has been exceeded with this unit.

6.3 Analog output

The analogue output is used to pass on a measured value. The selection of the signals happens
under program number 23, so PN23=0 corresponds to the 0-10 V signal and PN=1 corresponds
to the 0-20 mA signal. The analogue output is parameterised via the two program numbers

PN20 end value

(full scale) and

PN21 initial value

(offset). With the offset value, the value is

set at which the analogue output shows its minimum value (e.g. 4 mA) and with the full scale, the
value at which the output shows its maximum value (e.g. 20 mA).
It is possible in this way to rescale the input signal of a measuring transducer or even to convert
it into another standard signal.
The analogue output can be deactivated or activated via the

PN22 control value

. Furthermore,

the analogue output signal can either be allocated to the

current value

(with possible taring),

the

min-value

, the

max-value

, the

Hold-value

or the

absolute value

(without possible taring).

The analogue output is updated in the cycle of the measuring time (PN14) and has, at maximum,
a resolution of 12bit (4096 dots) and, at minimum, the resolution of the selected output range
PN20 – PN21. In other words, if the difference between PN20 and PN21 is less than 4096, the
resolution of the analogue output is reduced to PN20–PN21 dots!

6.4 Digital input

With the digital input, a wide variety of special functions can be triggered in the unit. These
include various taring and calibration functions, the Hold-function and switching over of the
display mode. The digital input can either be controlled actively with a 24 VDC signal or
passively via a potential-free contact.

6.4.1 Event counter

Since a change made to the configuration opens the door to access calibratable areas, changes
are recorded in an event counter. The event counter counts only when a change is made to the
relevant configuration sections. This is displayed when the system is started up, as e.g.
"C.0023", in order to allow the operating staff and quality management staff to check the
configuration status.

6.4.2 Taring or calibration

Taring or calibration can be carried out via the 4th key on the front or the digital input on terminal
12.
The unit can, on being switched on, be set to various modes via program numbers. Furthermore,
it is possible to differentiate between the evaluation of the key on the front and the digital input.
The tare key on the front and the digital input are interrogated independently of one another. For
taring, the 4th key, the digital input or both in parallel can be used.

Содержание IPM5

Страница 1: ...2 of measuring range are noise free high long term and temperature stability 5 digit digital display with range from 9999 to 99999 digits free scaling and setting of decimal point alignment of a senso...

Страница 2: ...ndex D version D 4 wire sensor M 6 wire sensor W Switching points 0 no switching points Number of digits 2 2 relay outputs 5 digits 5 4 4 relay outputs Interface Mechanical options none 0 7 IP65 foil...

Страница 3: ...calibration 6 4 3 Adjustment with 80 calibration IPM5 6 4 4 Sensitivity recognition 6 4 5 Automatical calibration 6 4 6 Taring 6 4 7 Hold function 6 5 Interfaces RS232 RS485 7 Programming 7 1 Program...

Страница 4: ...of 4 relays are available to monitor the threshold values Data from and to the device can be transmitted via the serial interface The IPM5 has a 4 wire connection with an additional calibration contac...

Страница 5: ...ching points 1 LED per switching point Overflow horizontal bars at the top Underflow horizontal bars at the bottom Display time 0 1 to 10 0 seconds Strain gauge input Measuring range Metering precisio...

Страница 6: ...pecific ASCII RS232 9600 Baud no parity 8 data bit 1 stop bit Cable length max 3 m RS485 9600 Baud no parity 8 data bit 1 stop bit Cable length max 1000 m Power pack Voltage supply 100 240 VAC 50 60 H...

Страница 7: ...e wheeling diodes Keep input output and supply lines separate from one another and do not lay them parallel with each other Position go and return lines next to one another Where possible use twisted...

Страница 8: ...5 IPW5 Gap for physical unit 1 After removing the fixing elements insert the device 2 Check the seal to make sure it fits securely 3 Click the fixing elements back into place and tighten the clamping...

Страница 9: ...or strip RS232 41 42 43 GND RS TxD RxD or RS485 41 42 43 GND RS Data B Data A The lines of the RS232 interface need to be connected 1 1 TxD to TxD and RxD to RxD RxD TxD GND RxD TxD GND IPW5 IPM5 PC o...

Страница 10: ...th a calibration wire CAL Mass pressure sensors which frequently have an additional wire for the artificial unbalance 80 of the bridge can be automatically calibrated via terminal 7 Examples of the co...

Страница 11: ...e 100 240 VAC 9 5 Electrical connection 100 240 VAC 2 3 4 5 6 7 8 9 10 11 In 2 In 3 In 4 In 5 In 6 In 7 Strain gauge input Analog output Digital input In 1 1 12 L 13 Auxiliary voltage 14 N Din 2 3 4 5...

Страница 12: ...ustable Unit C F Pt100 thermocouple Switchpoint displays 2 Optical limit value report 4 LED red Keys 5 6 7 and 3 Programming mode Increase range of value Reduce range of value Select next lower progra...

Страница 13: ...in value Erase the value that is shown in the display by simultaneously operating the and keys The erasure is acknowledged by horizontal bars The content of the memory will be lost with switching off...

Страница 14: ...on below the threshold and switched off on reaching the threshold Switching on delay The relay S1 S4 is on 10 seconds after reaching the threshold briefly exceeding the threshold does not lead to the...

Страница 15: ...nt value with possible taring the min value the max value the Hold value or the absolute value without possible taring The analogue output is updated in the cycle of the measuring time PN14 and has at...

Страница 16: ...he second run the calibration is carried out in the relevant measuring zone The procedure is as follows Sensitivity recognition Display of SEnS for the entire process Amplification of the measuring in...

Страница 17: ...offset nor end value are within the measuring range CErr2 if the end value is not at least 1 of measuring range greater than offset CErr3 if the end value is outside the measuring range CErr4 if the...

Страница 18: ...ransmitted so that the output can be displayed directly on a terminal or processed by a SPS Zeros at the front are suppressed during transmission With an overflow or underflow the display transmits ho...

Страница 19: ...ommand is sent the display will acknowledge this with an via the interface Under normal conditions the display does not send an acknowledgement back Only when the value is called up or the acknowledge...

Страница 20: ...number Change to the next program number Program number is displayed Change read the deposited parameters in the program Flashing of the least significant digit Save parameter Save the complete range...

Страница 21: ...d parameters are displayed In this case it is 75 640 7 1 Programming procedure The entire programming of the IPM5 IPW5 is done by the steps described below Change to programming mode Push the P key to...

Страница 22: ...sume the figure has to be changed from 75 640 to 75 000 Briefly push the P key to move to the next digit The 4 begins to flash Change the figure by pushing or key to change the digit from 4 to 0 Brief...

Страница 23: ...sensors and the corresponding display value programmed under the following program numbers PN101 PN105 The sensor signal must be parameterised with a strictly monotonous rising configuration A gap of...

Страница 24: ...ller than the offset setting PN2 It must differ from its measured value by at least 1 of the measuring range of the programmed offset value in PN2 If a standard sensor has been selected PN0 2 3 or 4 t...

Страница 25: ...conds With the static taring PN6 5 the taring operation is performed with an upward slope and held until the signal is taken away again After that the absolute value is displayed This function is espe...

Страница 26: ...ered direct after returning from the programming mode by confirming PN9 Calibration point PN10 Calibration point PN10 gives the percentage target value for the end value calibration As a rule 100 00 i...

Страница 27: ...the trigger is returned again PN16 8 has a special status because here no min max values can be called up via or key This mode is particularly necessary with calibrated balances due to the possibility...

Страница 28: ...ameter 59 95 X X X X X X Set value for taring 7 X X X X X Interfaces parameter Device option 32 34 X X X X Analog output parameter Device option 20 23 X X X X Measuring input parameter 0 18 X X X Line...

Страница 29: ...e various parameters is given in section 6 2 Relays The program numbers are also available when no relays are carried out in the unit In such cases only the relevant alarm LED light up on the front of...

Страница 30: ...99 0 2 3 Places after decimal point 0 4 none 2 5 Offset displacement 9999 99999 0 2 6 Taring function 0 no taring 1 permanent taring 2 transient taring 3 quick transient taring without report 4 perman...

Страница 31: ...1 10 0 1 0 2 14 Measuring time 0 01 10 00 1 00 2 15 Display mode 1 current measurand 2 min value 3 max value 4 Hold value 5 absolute value 1 2 16 Trigger for display change 0 none 1 absolute value st...

Страница 32: ...at exceedance of output area PN20 21 4 switch to smallest value 0x0000 at exceedance of output area PN20 21 5 switch to final value at converter over underflow wire break bars 6 switch to initial val...

Страница 33: ...0 no flashing 1 flashes at 1 2 flashes at 2 3 flashes at 3 4 flashes at 4 5 flashes at 1 or 2 6 flashes at 3 or 4 7 flashes at 1 2 3 or 4 0 5 Switchpoint 1 60 Switchpoint 1 0 deactivated 1 current me...

Страница 34: ...rror 1 5 81 Threshold 9999 99999 1000 6 82 Hysteresis 0 99999 0 5 83 Operation type quiescent current operating current 0 quiescent current 1 operating current 1 5 84 Switching delay 0 0 10 0 seconds...

Страница 35: ...return the unit to a defined basic state a reset can be carried out to the default values The following procedure should be used Switch off the power supply Press button P Switch on the power supply a...

Страница 36: ...n 9999 3 The display shows HELP in the 7 segment display The device located an error in the configuration memory carry out a reset to default values and reconfigure the device according to your applic...

Отзывы: