background image

 

 

 

j. 

Before servicing, allow furnace to cool. Always shut off 
electricity and fuel to furnace when servicing. This will 
prevent electrical shock or burns;

 

k. 

Seal supply and return air ducts; 

l. 

The vent system 

MUST

 be checked to determine that it is 

the correct type and size; 

m.  Install correct filter type and size; 

n. Unit 

MUST

 be installed so that electrical components are 

protected from direct contact with water. 

 

1.2.1 Safety 

Rules 

 

Your unit is built to provide many years of safe and 
dependable service provided it is properly installed and 
maintained. However, abuse and/or improper use can shorten 
the life of the unit and create hazards for you, the owner. 

 

a.  The U.S. Consumer Product Safety Commission 

recommends that users of oil-burning appliances install 
carbon monoxide detectors. There can be various 
sources of carbon monoxide in a building or dwelling. The 
sources could be gas-fired clothes dryers, gas cooking 
stoves, water heaters, furnaces, gas-fired fireplaces, 
wood fireplaces, and several others. Carbon monoxide 
can cause death and/or serious bodily injury. Therefore, 
to help alert people of potentially dangerous carbon 
monoxide levels, you should have carbon monoxide 
detectors listed by a nationally recognised agency 
(Underwriters Laboratories or International Approval 
Services) installed and maintained in the building or 
dwelling (see Note below). 

b.  There can be numerous sources of fire or smoke in a 

building or dwelling. Fire or smoke can cause death, 
serious bodily injury, and/or property damage. Therefore, 
in order to alert people to potentially dangerous fire or 
smoke, you should have fire and smoke detectors listed 
by Underwriters Laboratories installed and maintained in 
the building or dwelling (see Note below). 

 

NOTE:

 The manufacturer of your furnace does not test 

any detectors and makes no representations regarding 
any brand or type of detector. 

 

CAUTION 

Ensure that the area around the combustion air intake 
terminal is free of snow, ice and debris

 

CAUTION 

An air pressure switch MUST be used when the furnace 
is side-wall vented. 

 

CAUTION 

Do not use any commercially available soot remover. 
This furnace has a ceramic fibre type of combustion 
chamber. Normal servicing of this unit does not require 
the cleaning of same. Use extreme caution if for any 
reason you have to work in the area of the combustion 
chamber. 

 

 

 

1.2.2 

Freezing Temperature and Your Structure 

 

WARNING 

 

Freezing temperature warning. 

 

Turn off water supply. 

 

If your heater remains shut off during cold weather, 
the water pipes could freeze and burst, resulting in 
serious water damage. 

 

Your unit is equipped with safety devices that may keep it from 
operating if sensors detect abnormal conditions such as 
exhaust flues obstructed by snow, ice or debris. 

 

If the structure is unattended during cold weather you should 
take the following precautions: 

a.  Turn off main water supply into the structure and drain the 

water lines if possible. Open faucets in appropriate areas; 

b.  Have someone check the structure frequently during cold 

weather to make sure it is warm enough to prevent pipes 
from freezing. Contact a qualified service agency, if 
required. 

 

1.2.3 Installation 

regulations 

 

All local and national code requirements governing the 
installation of oil burning equipment, wiring and flue 
connections MUST be followed. Some of the codes that may 
be applicable are:  

 

CSA B139

 

Installation Code for Oil Burning 
Equipment 

NFPA 31

 

Installation of Oil Burning Equipment 

ANSI/NFPA 90B

 

Warm Air Heating and Air Conditioning 
Systems 

ANSI/NFPA 70

 

National Electrical Code 

CSA C22.1

 

Canadian Electrical Code 

 

Only the latest issues of the above codes should be used. 

 

1.3 

POSITIONING THE FURNACE 

 

CAUTION 

Carefully check your furnace upon delivery for any 
evidence of damage that may have occurred during 
shipping and handling. Any claims for damages or lost 
parts must be made with the transport company. 

 

1.3.1 Location 

 

The unit must be installed in a location where the 
ambient and return air temperatures are over 15

°

(60

°

F). 

 

Position the furnace as closely as possible to the 
chimney or vent terminal, providing ample clearance to 
permit easy accessibility for cleaning the inside of the 
furnace, the removal of filters, blower, motors, controls 
and flue connections.  

Содержание OLR105A12D

Страница 1: ...FOR THE INSTALLATION AND SERVICING OF THE FURNACE AND KEEP THE DOCUMENT NEAR THE UNIT FOR FUTURE REFERENCE HOMEOWNER PLEASE KEEP THIS MANUAL NEAR THE FURNACE FOR FUTURE REFERENCE Printed in Canada Pr...

Страница 2: ...ith the proper tools and test instruments Failure to carefully read and follow all instructions in this manual can result in death bodily injury and or property damage WARNING Fire hazard The furnace...

Страница 3: ...hen the furnace is side wall vented CAUTION Do not use any commercially available soot remover This furnace has a ceramic fibre type of combustion chamber Normal servicing of this unit does not requir...

Страница 4: ...maximum efficiency and without the use of a side wall power vent The unit will operate at a positive overfire draft and flue draft 1 4 2 Chimney installations When set up for chimney venting this furn...

Страница 5: ...all and the terminal is designed to fit through a minimum 2 x 8 joist space c Incorporates a vent blockage safety shutdown system If the vent or intake opening ever becomes partially or fully blocked...

Страница 6: ...ion 6 7 3 4 of the NFPA 31 CAUTION Most codes have a notwithstanding clause that states that products of combustion shall not enter the dwelling under any circumstances even if all other code requirem...

Страница 7: ...ER SLEEVE BACK 5 THREAD SPIN SLEEVE BACK 10 CUT STAINLESS STEEL CORE BACK BY 3 FIGURE 1 3 FIGURE 1 4 FIGURE 1 1 FIGURE 1 2 DRIVE THREE STAINLESS STEEL SCREWS STARTING NEAR TOP FIGURE 1 5 FIGURE 1 6 8...

Страница 8: ...RE 1 7 FIGURE 1 8 SEALANT FLOWING OUT FROM UNDER BAND CLAMP AT TERMINAL SEALANT OUTFLOW FIGURE 1 11 APPLY THE SEALANT TO THE TUBE END 9 SEALANT FLOWING OUT FROM UNDER BAND CLAMP AT BREECH SEALANT OUTF...

Страница 9: ...EEVE TIGHTLY INTO RECESS INSTALL STABILIZER SHROUD CAULK TO SEAL STABILIZER SHROUD TO THE WALL FIGURE 1 13 FIGURE 1 14 FIGURE 1 12 VENT TERMINAL PRESSURE SWITCH REFER TO WIRING DIAGRAM FOR ELECTRICAL...

Страница 10: ...to expose the corrugated stainless steel core 4 Cut the corrugated stainless steel core back by 76 mm 3 on the IFV Series vent You should now have about 76 mm 3 of insulation hanging out past the stai...

Страница 11: ...sult in death or personal injury 1 5 1 General Oil furnaces must have an adequate supply of combustion air It is common practice to assume that older homes have sufficient infiltration to accommodate...

Страница 12: ...and Solvent Cement ASTM D 2564 ABS Pipe and Fittings ASTM D 2235 Procedure for Cementing Joints ASTM D 2855 Additional parts required not included in VTK kit a 3 elbow fitting as required b 3 plastic...

Страница 13: ...d a Remove drawer assembly or air tube combination b Install nozzle see specifications c Confirm electrode settings d Make the electrical connections e Complete oil line connections CAUTION Do not tur...

Страница 14: ...5 Amp maximum to an Electronic Air Cleaner EAC Power will be available to the EAC at all times so it must incorporate a flow proving switch if it is to be wired into the furnace control box Most mode...

Страница 15: ...t purges the combustion chamber and vent for a pre set time 15 seconds The ignition transformer also continues to spark for this time period 10 During the post purge cycle the Fan Limit Control cools...

Страница 16: ...he blockage still exists the thermostat is again opened and the burner post purges again The post purge function thus becomes an inherent anti short cycling device 4 The unit will essentially go into...

Страница 17: ...n air temperature from the supply air temperature 5 If the temperature rise exceeds the temperature specified in Tables 4 1 to 4 3 change to the next higher blower speed tap until the temperature rise...

Страница 18: ...Smoke Test and allow for the 1 5 CO2 operating play required by the instructions 5 If the burner still does not shut down before a 1 smoke occurs check for a blockage of the pressure hose or at the h...

Страница 19: ...ever if you notice scaling in the radiator you should remove it The wrap around radiator can now be cleaned entirely from the front inspection port The furnace also has external clean out ports so the...

Страница 20: ...gn matter from the retention head and electrodes If a Beckett AFG burner has been installed the burner will have to be removed to check the retention head 3 1 4 Nozzle Replace the nozzle with the one...

Страница 21: ...elephone Day Night Dealer name and address START UP TEST RESULTS Nozzle Pressure lbpsi Burner adjustments Primary air Fine air Drawer assembly CO2 Smoke scale Bacharach Gross stack temperature F Ambie...

Страница 22: ...Burner tube insertion lenght inches Nozzle Delavan 0 50 60W 0 50 60W 0 60 60W 0 75 70B 0 85 70B 1 00 70B Pump pressure PSIG 130 140 160 130 130 130 Combustion air adjustment screw dial or dial only 3...

Страница 23: ...From ASHRAE 103 standard and US regulation 81 5 81 0 80 3 82 2 81 5 80 3 BECKETT BURNER SIDE WALL INSTALLATION Burner tube insertion lenght inches Nozzle Delavan 0 50 60W 0 50 60W 0 60 60W 0 75 70B 0...

Страница 24: ...m ASHRAE103 standard and US regulation 81 5 81 0 81 0 BECKETT BURNER SIDE WALL INSTALLATION Burner tube insertion lenght inches Nozzle Delavan 0 50 60W 0 50 60W 0 60 60W Pump pressure PSIG 130 140 160...

Страница 25: ...DNS 0571 Rev C DNS 0573 Rev C FIGURE 5 1 Model OLR105A12D FIGURE 5 2 Model OLR160B20C 26...

Страница 26: ...FIGURE 5 3 Model OUF105A12C FIGURE 5 4 Model OUF160B18C DNS 0572 Rev D DNS 0568 Rev C 27...

Страница 27: ...FIGURE 5 5 Model OLF105A12C DNS 0570 Rev C FIGURE 5 6 Model NOUF105A12D DNS 0674 Rev E 28...

Страница 28: ...FIGURE 5 7 Model NOLF105A12D DNS 0676 Rev D 29...

Страница 29: ...FIGURE 6 Wiring diagram OLR105A12D OLR160B20C OUF105A12C NOUF105A12D OUF160B18C OLF105A12C NOLF105A12D 30...

Страница 30: ...COMPONENTS AND REPLACEMENT PARTS 31...

Страница 31: ...PARTS LIST Model OLR105A12D B50031 B 32...

Страница 32: ...pplication 28B B30515 3 breech plate direct vent application 29 B30415 02 Gasket heat exchanger 30 B30808 01 Electrical box cover 31 B30828 Electrical box box only 32 L07F003 Rocker switch SPST consta...

Страница 33: ...PARTS LIST Model OLR160B20C B50032 C 34...

Страница 34: ...e panel assembly 30 B30686 01 Right side panel insulation 31 B30668 01 Right bottom filter support 32 B30835 Right top filter support 33 B30782 01 Front panel assembly labels included without logo 34...

Страница 35: ...PARTS LIST Model OUF105A12C B50033 B 36...

Страница 36: ...r 23 F07O001 Hexagonal flange nut 3 8 16NC brass 24 F07F024 Hexagonal nut 3 8 16NC brass 25 F06F005 Washer 3 8 AA zinc 26 L05F011 Terminal strip 6 positions 27 B30808 01 Electrical box cover 28 L01H00...

Страница 37: ...PARTS LIST Model OUF160B18C B50034 D 38...

Страница 38: ...nt panel assembly labels included 29 B30779 Front panel insulation 30 B30651 Blower door assembly labels included without logo 31 Z99F050 Door handle 32 F06F005 Washer 3 8 AA zinc 33 F07F024 Hexagonal...

Страница 39: ...PARTS LIST Model OLF105A12C B50035 B 40...

Страница 40: ...61 Sight glass 27 F07O001 Hexagonal flange nut 3 8 16NC brass 28A B30459 5 breech plate chimney application 28B B30515 3 breech plate direct vent application 29 B30415 02 Gasket heat exchanger 30 B308...

Страница 41: ...PARTS LIST Model NOLF105A12D B50037 B 42...

Страница 42: ...ech plate direct vent application 28 B30415 02 Gasket heat exchanger 29 B30808 01 Electrical box cover 30 B30826 Electrical box box only 31 L07F003 Rocker switch SPST constant blower operation 32 R02I...

Страница 43: ...PARTS LIST Model NOUF105A12D B50036 B 44...

Страница 44: ...3 8 16NC brass 24 F07F024 Hexagonal nut 3 8 16NC brass 25 Z99F050 Door handle 26 L05F011 Terminal strip 6 positions 27 B30808 01 Electrical box cover 28 L01H009 Relay SPDT 24VAC 29 L01F009 Transforme...

Отзывы: