Removing the firepot
The firepot is seldom replaced, but when it must be replaced
one must simply:
1. Remove
the
burner;
2. Remove the burner Limit Control;
3. Remove the breech plate;
4. Remove the front panel;
5. Remove the brass nuts on the stainless steel heat
exchanger studs;
6. Pry the bottom half of the heat exchanger apart by using
the designated prying tabs;
7. Remove the bottom half of the heat exchanger through
the front of the furnace;
8. Pull the firepot up and out of the bottom half of the heat
exchanger;
9. Remove the old sealing gasket from the flange of the
upper half of the heat exchanger;
10. Scrape any residual gasket material off the matching
flanges of the heat exchanger.
Replacing the firepot
1. Align the slot at the front part of the firepot with the burner
tube sleeve and gently lower the firepot into the bottom
half of the heat exchanger;
2. Holding the firepot near the perimeter, gently push the
firepot all the way into the bottom half of the heat
exchanger until it is properly seated;
3. Thoroughly wet the gasket with water using a spray pump
bottle, position the tabs over the studs, and push the
gasket upward against the sealing flange of the upper half
of the heat exchanger;
4. Install the brass nuts on the studs by engaging only 2 or 3
threads;
5. Position the bottom half of the heat exchanger under the
upper half and align the bottom half so that the slots in the
bolting tabs engage the stainless steel studs. There is no
further need to hold onto the bottom half as it will now be
suspended on the stud nuts;
6. Push upward on the housing and thread the nuts finger-
tight as far as possible;
7. Intermittently tighten the brass nuts with a wrench in a
sequence that will pull the heat exchanger halves
together evenly. Tighten all nuts to 90 inch-lbs torque
once and then alternately re-tighten all nuts again to 100
inch-lb.
THE RE-TIGHTENING SEQUENCE IS
ABSOLUTELY NECESSARY TO ENSURE A TIGHT
JOINT
;
8. Re-assemble the front panel, breech plate, Limit Control
and burner in reverse sequence to their removal;
9. Follow the instructions for starting the burner for the first
time to cure the firepot and perform combustion checks.
3.1.3) Drawer
assembly
Remove the drawer assembly. Clean all foreign matter from
the retention head and electrodes. If a Beckett AFG burner
has been installed, the burner will have to be removed to
check the retention head.
3.1.4) Nozzle
Replace the nozzle with the one specified in Tables 4.1 to 4.3.
3.1.5) Oil
filter
Tank filter
The tank filter should be replaced as required.
Secondary filter
The 10 micron (or less) filter cartridges should be replaced
annually.
3.1.6) Air
filters
Air filters are the disposable type. They should be replaced at
least once a year. Dusty conditions, presence of animal hair
etc. may require more frequent filter changes. Dirty filters will
impact furnace efficiency and increase oil consumption.
3.1.7) Motor
lubrication
Do NOT lubricate the oil burner motor or the direct drive
blower motor as it is permanently lubricated.
3.1.8) CAS-2B combustion air kit
(chimney venting)
If used, check the CAS-2B combustion air kit for proper
operation. Check to see that the inlet screen is not plugged.
Block the air inlet completely and ensure that a zero smoke
reading results. If a zero smoke reading is not obtained, set up
the burner as indicated in Tables 4.1, 4.2 or 4.3.
Gradually block off the intake. The CO
2
should increase to a
maximum of 0.5 percentage points at the fully blocked
condition. If not, check that the VRV gate is pivoting freely and
that the pivot rod is in a horizontal position. Also, check that
the counterweight has been properly adjusted in accordance
with CAS-2B installation instructions.
3.1.9) BLOCKED VENT SHUT-OFF DEVICE (BVSO)
CLEANING
For continued safe operation, the Blocked Vent Shut-Off
System (BVSO) is required to be inspected and maintained
annually by a qualified technician.
1. Disconnect the power to the appliance;
2. Remove the two screws holding the BVSO assembly
cover in place;
3. Remove the cover;
4. Remove the two screws holding the control box to the
heat transfer tube assembly. Sliding the control box in the
appropriate direction will unlock it form the heat transfer
tube assembly;
5. Carefully remove any build-up from the thermal switch
surface;
CAUTION
Do not dent or scratch the surface of the thermal switch.
If the thermal switch is damaged, replacement is
required.
6.
Clear and remove any build-up or obstruction inside the
heat transfer tube;
7. Re-mount, lock and fasten the control box with the 2
screws removed in step 4;
8. Re-attach the assembly cover with the screws removed in
step 2;
9. Re-establish power to the appliance.
21
Содержание OLR105A12D
Страница 25: ...DNS 0571 Rev C DNS 0573 Rev C FIGURE 5 1 Model OLR105A12D FIGURE 5 2 Model OLR160B20C 26...
Страница 26: ...FIGURE 5 3 Model OUF105A12C FIGURE 5 4 Model OUF160B18C DNS 0572 Rev D DNS 0568 Rev C 27...
Страница 27: ...FIGURE 5 5 Model OLF105A12C DNS 0570 Rev C FIGURE 5 6 Model NOUF105A12D DNS 0674 Rev E 28...
Страница 28: ...FIGURE 5 7 Model NOLF105A12D DNS 0676 Rev D 29...
Страница 29: ...FIGURE 6 Wiring diagram OLR105A12D OLR160B20C OUF105A12C NOUF105A12D OUF160B18C OLF105A12C NOLF105A12D 30...
Страница 30: ...COMPONENTS AND REPLACEMENT PARTS 31...
Страница 31: ...PARTS LIST Model OLR105A12D B50031 B 32...
Страница 33: ...PARTS LIST Model OLR160B20C B50032 C 34...
Страница 35: ...PARTS LIST Model OUF105A12C B50033 B 36...
Страница 37: ...PARTS LIST Model OUF160B18C B50034 D 38...
Страница 39: ...PARTS LIST Model OLF105A12C B50035 B 40...
Страница 41: ...PARTS LIST Model NOLF105A12D B50037 B 42...
Страница 43: ...PARTS LIST Model NOUF105A12D B50036 B 44...