background image

 

 

Removing the firepot 

 

The firepot is seldom replaced, but when it must be replaced 
one must simply: 

 

1. Remove 

the 

burner; 

2.  Remove the burner Limit Control; 
3.  Remove the breech plate; 
4.  Remove the front panel; 
5.  Remove the brass nuts on the stainless steel heat 

exchanger studs; 

6.  Pry the bottom half of the heat exchanger apart by using 

the designated prying tabs; 

7.  Remove the bottom half of the heat exchanger through 

the front of the furnace; 

8.  Pull the firepot up and out of the bottom half of the heat 

exchanger; 

9.  Remove the old sealing gasket from the flange of the 

upper half of the heat exchanger; 

10. Scrape any residual gasket material off the matching 

flanges of the heat exchanger. 

 

Replacing the firepot 

 

1.  Align the slot at the front part of the firepot with the burner 

tube sleeve and gently lower the firepot into the bottom 
half of the heat exchanger; 

2.  Holding the firepot near the perimeter, gently push the 

firepot all the way into the bottom half of the heat 
exchanger until it is properly seated; 

3.  Thoroughly wet the gasket with water using a spray pump 

bottle, position the tabs over the studs, and push the 
gasket upward against the sealing flange of the upper half 
of the heat exchanger; 

4.  Install the brass nuts on the studs by engaging only 2 or 3 

threads; 

5.  Position the bottom half of the heat exchanger under the 

upper half and align the bottom half so that the slots in the 
bolting tabs engage the stainless steel studs. There is no 
further need to hold onto the bottom half as it will now be 
suspended on the stud nuts; 

6.  Push upward on the housing and thread the nuts finger-

tight as far as possible; 

7.  Intermittently tighten the brass nuts with a wrench in a 

sequence that will pull the heat exchanger halves 
together evenly. Tighten all nuts to 90 inch-lbs torque 
once and then alternately re-tighten all nuts again to 100 
inch-lb. 

THE RE-TIGHTENING SEQUENCE IS 

ABSOLUTELY NECESSARY TO ENSURE A TIGHT 
JOINT

8.  Re-assemble the front panel, breech plate, Limit Control 

and burner in reverse sequence to their removal; 

9.  Follow the instructions for starting the burner for the first 

time to cure the firepot and perform combustion checks. 

 

3.1.3) Drawer 

assembly 

 

Remove the drawer assembly. Clean all foreign matter from 
the retention head and electrodes. If a Beckett AFG burner 
has been installed, the burner will have to be removed to 
check the retention head. 

 

 

3.1.4) Nozzle 

 

Replace the nozzle with the one specified in Tables 4.1 to 4.3. 

 

3.1.5) Oil 

filter 

 

Tank filter 

The tank filter should be replaced as required.  

 

Secondary filter 

The 10 micron (or less) filter cartridges should be replaced 
annually. 

 

3.1.6) Air 

filters 

 

Air filters are the disposable type. They should be replaced at 
least once a year. Dusty conditions, presence of animal hair 
etc. may require more frequent filter changes. Dirty filters will 
impact furnace efficiency and increase oil consumption. 

 

3.1.7) Motor 

lubrication 

 

Do NOT lubricate the oil burner motor or the direct drive 
blower motor as it is permanently lubricated.  

 

3.1.8)  CAS-2B combustion air kit 

(chimney venting) 

 

If used, check the CAS-2B combustion air kit for proper 
operation. Check to see that the inlet screen is not plugged. 
Block the air inlet completely and ensure that a zero smoke 
reading results. If a zero smoke reading is not obtained, set up 
the burner as indicated in Tables 4.1, 4.2 or 4.3.  

 

Gradually block off the intake. The CO

2

 should increase to a 

maximum of 0.5 percentage points at the fully blocked 
condition. If not, check that the VRV gate is pivoting freely and 
that the pivot rod is in a horizontal position. Also, check that 
the counterweight has been properly adjusted in accordance 
with CAS-2B installation instructions. 

 

3.1.9)  BLOCKED VENT SHUT-OFF DEVICE (BVSO) 

CLEANING 

 

For continued safe operation, the Blocked Vent Shut-Off 
System (BVSO) is required to be inspected and maintained 
annually by a qualified technician. 

1.  Disconnect the power to the appliance; 

2.  Remove the two screws holding the BVSO assembly 

cover in place; 

3.  Remove the cover; 

4.  Remove the two screws holding the control box to the 

heat transfer tube assembly. Sliding the control box in the 
appropriate direction will unlock it form the heat transfer 
tube assembly; 

5.  Carefully remove any build-up from the thermal switch 

surface; 

 

CAUTION 

Do not dent or scratch the surface of the thermal switch. 
If the thermal switch is damaged, replacement is 
required. 

 

 

6. 

Clear and remove any build-up or obstruction inside the 
heat transfer tube; 

7.  Re-mount, lock and fasten the control box with the 2 

screws removed in step 4; 

8.  Re-attach the assembly cover with the screws removed in 

step 2; 

9.  Re-establish power to the appliance. 

21 

Содержание OLR105A12D

Страница 1: ...FOR THE INSTALLATION AND SERVICING OF THE FURNACE AND KEEP THE DOCUMENT NEAR THE UNIT FOR FUTURE REFERENCE HOMEOWNER PLEASE KEEP THIS MANUAL NEAR THE FURNACE FOR FUTURE REFERENCE Printed in Canada Pr...

Страница 2: ...ith the proper tools and test instruments Failure to carefully read and follow all instructions in this manual can result in death bodily injury and or property damage WARNING Fire hazard The furnace...

Страница 3: ...hen the furnace is side wall vented CAUTION Do not use any commercially available soot remover This furnace has a ceramic fibre type of combustion chamber Normal servicing of this unit does not requir...

Страница 4: ...maximum efficiency and without the use of a side wall power vent The unit will operate at a positive overfire draft and flue draft 1 4 2 Chimney installations When set up for chimney venting this furn...

Страница 5: ...all and the terminal is designed to fit through a minimum 2 x 8 joist space c Incorporates a vent blockage safety shutdown system If the vent or intake opening ever becomes partially or fully blocked...

Страница 6: ...ion 6 7 3 4 of the NFPA 31 CAUTION Most codes have a notwithstanding clause that states that products of combustion shall not enter the dwelling under any circumstances even if all other code requirem...

Страница 7: ...ER SLEEVE BACK 5 THREAD SPIN SLEEVE BACK 10 CUT STAINLESS STEEL CORE BACK BY 3 FIGURE 1 3 FIGURE 1 4 FIGURE 1 1 FIGURE 1 2 DRIVE THREE STAINLESS STEEL SCREWS STARTING NEAR TOP FIGURE 1 5 FIGURE 1 6 8...

Страница 8: ...RE 1 7 FIGURE 1 8 SEALANT FLOWING OUT FROM UNDER BAND CLAMP AT TERMINAL SEALANT OUTFLOW FIGURE 1 11 APPLY THE SEALANT TO THE TUBE END 9 SEALANT FLOWING OUT FROM UNDER BAND CLAMP AT BREECH SEALANT OUTF...

Страница 9: ...EEVE TIGHTLY INTO RECESS INSTALL STABILIZER SHROUD CAULK TO SEAL STABILIZER SHROUD TO THE WALL FIGURE 1 13 FIGURE 1 14 FIGURE 1 12 VENT TERMINAL PRESSURE SWITCH REFER TO WIRING DIAGRAM FOR ELECTRICAL...

Страница 10: ...to expose the corrugated stainless steel core 4 Cut the corrugated stainless steel core back by 76 mm 3 on the IFV Series vent You should now have about 76 mm 3 of insulation hanging out past the stai...

Страница 11: ...sult in death or personal injury 1 5 1 General Oil furnaces must have an adequate supply of combustion air It is common practice to assume that older homes have sufficient infiltration to accommodate...

Страница 12: ...and Solvent Cement ASTM D 2564 ABS Pipe and Fittings ASTM D 2235 Procedure for Cementing Joints ASTM D 2855 Additional parts required not included in VTK kit a 3 elbow fitting as required b 3 plastic...

Страница 13: ...d a Remove drawer assembly or air tube combination b Install nozzle see specifications c Confirm electrode settings d Make the electrical connections e Complete oil line connections CAUTION Do not tur...

Страница 14: ...5 Amp maximum to an Electronic Air Cleaner EAC Power will be available to the EAC at all times so it must incorporate a flow proving switch if it is to be wired into the furnace control box Most mode...

Страница 15: ...t purges the combustion chamber and vent for a pre set time 15 seconds The ignition transformer also continues to spark for this time period 10 During the post purge cycle the Fan Limit Control cools...

Страница 16: ...he blockage still exists the thermostat is again opened and the burner post purges again The post purge function thus becomes an inherent anti short cycling device 4 The unit will essentially go into...

Страница 17: ...n air temperature from the supply air temperature 5 If the temperature rise exceeds the temperature specified in Tables 4 1 to 4 3 change to the next higher blower speed tap until the temperature rise...

Страница 18: ...Smoke Test and allow for the 1 5 CO2 operating play required by the instructions 5 If the burner still does not shut down before a 1 smoke occurs check for a blockage of the pressure hose or at the h...

Страница 19: ...ever if you notice scaling in the radiator you should remove it The wrap around radiator can now be cleaned entirely from the front inspection port The furnace also has external clean out ports so the...

Страница 20: ...gn matter from the retention head and electrodes If a Beckett AFG burner has been installed the burner will have to be removed to check the retention head 3 1 4 Nozzle Replace the nozzle with the one...

Страница 21: ...elephone Day Night Dealer name and address START UP TEST RESULTS Nozzle Pressure lbpsi Burner adjustments Primary air Fine air Drawer assembly CO2 Smoke scale Bacharach Gross stack temperature F Ambie...

Страница 22: ...Burner tube insertion lenght inches Nozzle Delavan 0 50 60W 0 50 60W 0 60 60W 0 75 70B 0 85 70B 1 00 70B Pump pressure PSIG 130 140 160 130 130 130 Combustion air adjustment screw dial or dial only 3...

Страница 23: ...From ASHRAE 103 standard and US regulation 81 5 81 0 80 3 82 2 81 5 80 3 BECKETT BURNER SIDE WALL INSTALLATION Burner tube insertion lenght inches Nozzle Delavan 0 50 60W 0 50 60W 0 60 60W 0 75 70B 0...

Страница 24: ...m ASHRAE103 standard and US regulation 81 5 81 0 81 0 BECKETT BURNER SIDE WALL INSTALLATION Burner tube insertion lenght inches Nozzle Delavan 0 50 60W 0 50 60W 0 60 60W Pump pressure PSIG 130 140 160...

Страница 25: ...DNS 0571 Rev C DNS 0573 Rev C FIGURE 5 1 Model OLR105A12D FIGURE 5 2 Model OLR160B20C 26...

Страница 26: ...FIGURE 5 3 Model OUF105A12C FIGURE 5 4 Model OUF160B18C DNS 0572 Rev D DNS 0568 Rev C 27...

Страница 27: ...FIGURE 5 5 Model OLF105A12C DNS 0570 Rev C FIGURE 5 6 Model NOUF105A12D DNS 0674 Rev E 28...

Страница 28: ...FIGURE 5 7 Model NOLF105A12D DNS 0676 Rev D 29...

Страница 29: ...FIGURE 6 Wiring diagram OLR105A12D OLR160B20C OUF105A12C NOUF105A12D OUF160B18C OLF105A12C NOLF105A12D 30...

Страница 30: ...COMPONENTS AND REPLACEMENT PARTS 31...

Страница 31: ...PARTS LIST Model OLR105A12D B50031 B 32...

Страница 32: ...pplication 28B B30515 3 breech plate direct vent application 29 B30415 02 Gasket heat exchanger 30 B30808 01 Electrical box cover 31 B30828 Electrical box box only 32 L07F003 Rocker switch SPST consta...

Страница 33: ...PARTS LIST Model OLR160B20C B50032 C 34...

Страница 34: ...e panel assembly 30 B30686 01 Right side panel insulation 31 B30668 01 Right bottom filter support 32 B30835 Right top filter support 33 B30782 01 Front panel assembly labels included without logo 34...

Страница 35: ...PARTS LIST Model OUF105A12C B50033 B 36...

Страница 36: ...r 23 F07O001 Hexagonal flange nut 3 8 16NC brass 24 F07F024 Hexagonal nut 3 8 16NC brass 25 F06F005 Washer 3 8 AA zinc 26 L05F011 Terminal strip 6 positions 27 B30808 01 Electrical box cover 28 L01H00...

Страница 37: ...PARTS LIST Model OUF160B18C B50034 D 38...

Страница 38: ...nt panel assembly labels included 29 B30779 Front panel insulation 30 B30651 Blower door assembly labels included without logo 31 Z99F050 Door handle 32 F06F005 Washer 3 8 AA zinc 33 F07F024 Hexagonal...

Страница 39: ...PARTS LIST Model OLF105A12C B50035 B 40...

Страница 40: ...61 Sight glass 27 F07O001 Hexagonal flange nut 3 8 16NC brass 28A B30459 5 breech plate chimney application 28B B30515 3 breech plate direct vent application 29 B30415 02 Gasket heat exchanger 30 B308...

Страница 41: ...PARTS LIST Model NOLF105A12D B50037 B 42...

Страница 42: ...ech plate direct vent application 28 B30415 02 Gasket heat exchanger 29 B30808 01 Electrical box cover 30 B30826 Electrical box box only 31 L07F003 Rocker switch SPST constant blower operation 32 R02I...

Страница 43: ...PARTS LIST Model NOUF105A12D B50036 B 44...

Страница 44: ...3 8 16NC brass 24 F07F024 Hexagonal nut 3 8 16NC brass 25 Z99F050 Door handle 26 L05F011 Terminal strip 6 positions 27 B30808 01 Electrical box cover 28 L01H009 Relay SPDT 24VAC 29 L01F009 Transforme...

Отзывы: