WF-2000 Series AIO
User’s Manual (Ver. 1.2, May./2014) ------------- 48
Table
5-4 A 16-bits word item
Value
1st
2nd
0x1234
0x12
0x34
5.3 Address Mapping
5.3.1
WF-2017 I/O Address Mapping
Table
5-5 (3xxxx) AI address
Begin Address
Points
Descriptions
Range
Access Type
30001
1~16
Analog Input
-32768 ~ +32767 (Bipolar)
0 ~ +65535 (Unipolar)
R
30017
1
AI Wire
Selected
0 ~ 1
0 => Differential
1 => Single-Ended
R
Table
5-6 (4xxxx) AO address
Begin Address
Points
Descriptions
Range
Access Type
40248
1
Reset System
1= Reset System
247= Restore to Factory
Default Settings
W
5.3.2
WF-2019 I/O Address Mapping
Table
5-7 (3xxxx) AI address
Begin Address
Points
Descriptions
Range
Access Type
30001
1~10
Analog Input
-32768 ~ +32767 (Bipolar)
0 ~ +65535 (Unipolar)
R
30011
1
CJC data
-300 ~ +1000
R