WF-2000 Series AIO
User’s Manual (Ver. 1.2, May./2014) ------------- 54
Type Code
Input Range
Data Format
+F.S
-F.S
Engineering Unit
+1300.0
-0270.0
15h
Type N
Thermocouple
-270
to
1300°C
2’s comp HEX
7FFFh
E56Bh
Engineering Unit
+2320.0
+0000.0
16h
Type C
Thermocouple
0
to
2320°C
2’s comp HEX
7FFFh
0000h
Engineering Unit
+20.000
+00.000
1Ah
0
to
+20 mA
2’s comp HEX
FFFFh
0000h
Note:
Getting the 7FFFh value in all of the thermocouple type codes, it means
that the thermocouple wires are broken.
A.2 Analog Output Type and Data Format Table
Type Code
Input Range
Data Format
+F.S
-F.S
Engineering Unit
+20.000
+00.000
30h
0
to
+20 mA
2’s comp HEX
FFFFh
0000h
Engineering Unit
+20.000
+04.000
31h
+4
to
+20 mA
2’s comp HEX
FFFFh
0000h
Engineering Unit
+10.000
+00.000
32h
0
to
+10 V
2’s comp HEX
FFFFh
0000h
Engineering Unit
+10.000
-10.000
33h
-10
to
+10 V
2’s comp HEX
7FFFh
8000h
Engineering Unit
+05.000
+00.000
34h
0
to
+5 V
2’s comp HEX
FFFFh
0000h
Engineering Unit
+05.000
-05.000
35h
-5
to
+5 V
2’s comp HEX
7FFFh
8000h