WF-2000 Series AIO
User’s Manual (Ver. 1.2, May./2014) ------------- 53
Type Code
Input Range
Data Format
+F.S
-F.S
Engineering Unit
+1.0000
-1.0000
0Ah
-1
to
+1 V
2’s comp HEX
7FFFh
8000h
Engineering Unit
+500.00
-500.00
0Bh
-500
to
+500 mV
2’s comp HEX
7FFFh
8000h
Engineering Unit
+150.00
-150.00
0Ch
-150
to
+150 mV
2’s comp HEX
7FFFh
8000h
Engineering Unit
+20.000
-20.000
0Dh
-20
to
+20 mA
2’s comp HEX
7FFFh
8000h
Engineering Unit
+760.00
-210.00
0Eh
Type J
Thermocouple
-210
to
760°C
2’s comp HEX
7FFFh
DCA2h
Engineering Unit
+1372.0
-0270.0
0Fh
Type K
Thermocouple
-270
to
1372°C
2’s comp HEX
7FFFh
E6D0h
Engineering Unit
+400.00
-270.00
10h
Type T
Thermocouple
-270
to
400°C
2’s comp HEX
7FFFh
A99Ah
Engineering Unit
1000.0
-0270.0
11h
Type E
Thermocouple
-270
to
1000°C
2’s comp HEX
7FFFh
DD71h
Engineering Unit
+1768.0
+0000.0
12h
Type R
Thermocouple
0
to
1768°C
2’s comp HEX
7FFFh
0000h
Engineering Unit
+1768.0
+0000.0
13h
Type S
Thermocouple
0
to
1768°C
2’s comp HEX
7FFFh
0000h
Engineering Unit
+1820.0
+0000.0
14h
Type B
Thermocouple
0
to
1820°C
2’s comp HEX
7FFFh
0000h