WF-2000 Series AIO
User’s Manual (Ver. 1.2, May./2014) ------------- 35
Power On Value of AO
The power on value of AO can be Set and Get in this
region. It is loaded into the AO under 3 conditions: power
on, reset by Module Watchdog, reset by reset command.
Enable:
Select which channel to enable or disable this
function.
Set Value:
Set the current output value as Power on
value.
Get Value:
Get the current configuration of Power on
value.
Safe Value of AO
The safe value of AO can be Set and Get in this region.
When the communication timeout occurs, the "Safe Value"
is loaded into the AO.
Enable:
Select which channel to enable or disable this
function.
Set Value:
Set the current output value as Safe Value.
Get Value:
Get the current configuration of Safe Value.
Active Time (ms):
This function is active
when the
communication timeout reach this setting.