WF-2000 Series AIO
User’s Manual (Ver. 1.2, May./2014) ------------- 49
Table
5-8 (4xxxx) AO address
Begin Address
Points
Descriptions
Range
Access Type
40248
1
Reset System
1= Reset System
247= Restore to Factory
Default Settings
W
5.3.3
WF-2026 I/O Address Mapping
Table
5-9 (3xxxx) AI address
Begin Address
Points
Descriptions
Range
Access Type
30001
1~5
Analog Input
-32768 ~ +32767 (Bipolar)
0 ~ +65535 (Unipolar)
R
Table
5-10 (4xxxx) AO address
Begin Address
Points
Descriptions
Range
Access Type
40001
1~2
Analog Output
-32768 ~ +32767 (Bipolar)
0 ~ +65535 (Unipolar)
R/W
Table
5-11 (4xxxx) AO address
Begin Address
Points
Descriptions
Range
Access Type
40248
1
Reset System
1= Reset System
247= Restore to Factory
Default Settings
W
Table
5-12 (0xxxx) DO address
Begin Address
Points
Descriptions
Range
Access Type
00001
1~3
Digital Output
0=OFF, 1=ON
R/W
Table
5-13 (1xxxx) DI address
Begin Address
Points
Descriptions
Range
Access Type
10001
1~2
Digital Input
0=OFF, 1=ON
R