2. DCON Protocol
All communication with tM modules consists of commands
generated by the host and responses transmitted by the tM
modules. Each module has a unique ID number that is used
for addressing purposes and is stored in non-volatile memory.
The ID is 01 by default and can be changed using a user
command. All commands to the modules contain the ID
address, meaning that only the addressed module will respond.
The only exception to this is commands #** (Section 2.2) and
~** (Section 2.24), which are sent to all modules, but in both
of these cases, the modules do not reply to the command.
Command Format:
Leading
Character
Module
Address
Command [CHKSUM] CR
Response Format:
Leading
Character
Module
Address
Data [CHKSUM]
CR
CHKSUM
A
2-character checksum which is present when
the checksum setting is enabled. See Sections
1.9 (Data Format Setting) and 2.1 for details.
CR
End of command character, carriage return
(0x0D)
tM Series DIO User Manual, Rev: A1.3 7PH-013-A13
36
ГК
Атлант
Инжиниринг
–
официальный
представитель
в
РФ
и
СНГ
+7(495)109-02-08 [email protected] www.bbrc.ru
Содержание tM Series
Страница 8: ...tM Series DIO User Manual Rev A1 3 7PH 013 A13 8 7 495 109 02 08 sales bbrc ru www bbrc ru...
Страница 9: ...tM Series DIO User Manual Rev A1 3 7PH 013 A13 9 7 495 109 02 08 sales bbrc ru www bbrc ru...
Страница 10: ...tM Series DIO User Manual Rev A1 3 7PH 013 A13 10 7 495 109 02 08 sales bbrc ru www bbrc ru...
Страница 11: ...tM Series DIO User Manual Rev A1 3 7PH 013 A13 11 7 495 109 02 08 sales bbrc ru www bbrc ru...
Страница 12: ...tM P3POR3 tM Series DIO User Manual Rev A1 3 7PH 013 A13 12 7 495 109 02 08 sales bbrc ru www bbrc ru...
Страница 13: ...tM R5 tM Series DIO User Manual Rev A1 3 7PH 013 A13 13 7 495 109 02 08 sales bbrc ru www bbrc ru...
Страница 22: ...1 5 Dimensions tM Series DIO User Manual Rev A1 3 7PH 013 A13 22 7 495 109 02 08 sales bbrc ru www bbrc ru...