3.7.10 Sub-function 41 (0x29) Set DI/O active states
This sub-function code is used to set the DI/O active states of a
module.
Request
00
Address
1 Byte
1 ~ 247
01
Function code
1 Byte
0x46
02
Sub-function code
1 Byte
0x29
03
DI/O active states
1 Byte
*0x00~0x03
Refer to the table below.
*0x00~0x03 for tM-P4C4
0x00 and 0x02 for tM-C8
0x00 and 0x01 for tM-P8
DI/O active states:
7 6 5 4 3 2 1 0
Reserved OAS
IAS
Key Description
OAS
DO active state
0: output value 1 for relay active
output value 0 for relay inactive
1: output value 0 for relay active
output value 1 for relay inactive
IAS
DI active state
0: input value 1 for non-signal or the low voltage;
input value 0 for high voltage
1: input value 0 for non-signal or the low voltage;
input value 1 for high voltage
Response
00
Address
1 Byte
1 ~ 247
01
Function code
1 Byte
0x46
02
Sub-function code
1 Byte
0x29
03
Power-on value
1 Byte
0x00: OK
others: error
tM Series DIO User Manual, Rev: A1.3 7PH-013-A13
125
ГК
Атлант
Инжиниринг
–
официальный
представитель
в
РФ
и
СНГ
+7(495)109-02-08 [email protected] www.bbrc.ru
Содержание tM Series
Страница 8: ...tM Series DIO User Manual Rev A1 3 7PH 013 A13 8 7 495 109 02 08 sales bbrc ru www bbrc ru...
Страница 9: ...tM Series DIO User Manual Rev A1 3 7PH 013 A13 9 7 495 109 02 08 sales bbrc ru www bbrc ru...
Страница 10: ...tM Series DIO User Manual Rev A1 3 7PH 013 A13 10 7 495 109 02 08 sales bbrc ru www bbrc ru...
Страница 11: ...tM Series DIO User Manual Rev A1 3 7PH 013 A13 11 7 495 109 02 08 sales bbrc ru www bbrc ru...
Страница 12: ...tM P3POR3 tM Series DIO User Manual Rev A1 3 7PH 013 A13 12 7 495 109 02 08 sales bbrc ru www bbrc ru...
Страница 13: ...tM R5 tM Series DIO User Manual Rev A1 3 7PH 013 A13 13 7 495 109 02 08 sales bbrc ru www bbrc ru...
Страница 22: ...1 5 Dimensions tM Series DIO User Manual Rev A1 3 7PH 013 A13 22 7 495 109 02 08 sales bbrc ru www bbrc ru...