3.7.8 Sub-function 39 (0x27) Set the power-on value
This sub-function code is used to set the power-on value of a module.
Request
00
Address
1 Byte
1 ~ 247
01
Function code
1 Byte
0x46
02
Sub-function code
1 Byte
0x27
03
Power-on Value
1 Byte
*0x00~0xFF
*0x00~0x0F for tM-P4C4
0x00~0xFF for tM-C8
Response
00
Address
1 Byte
1 ~ 247
01
Function code
1 Byte
0x46
02
Sub-function code
1 Byte
0x28
03
Power-on value
1 Byte
0x00: OK,
others: error
Error Response
00
Address
1 Byte
1 ~ 247
01
Function code
1 Byte
0xC6
02
Exception code
1 Byte
Refer to the Modbus standard for
more details.
tM Series DIO User Manual, Rev: A1.3 7PH-013-A13
123
ГК
Атлант
Инжиниринг
–
официальный
представитель
в
РФ
и
СНГ
+7(495)109-02-08 [email protected] www.bbrc.ru
Содержание tM Series
Страница 8: ...tM Series DIO User Manual Rev A1 3 7PH 013 A13 8 7 495 109 02 08 sales bbrc ru www bbrc ru...
Страница 9: ...tM Series DIO User Manual Rev A1 3 7PH 013 A13 9 7 495 109 02 08 sales bbrc ru www bbrc ru...
Страница 10: ...tM Series DIO User Manual Rev A1 3 7PH 013 A13 10 7 495 109 02 08 sales bbrc ru www bbrc ru...
Страница 11: ...tM Series DIO User Manual Rev A1 3 7PH 013 A13 11 7 495 109 02 08 sales bbrc ru www bbrc ru...
Страница 12: ...tM P3POR3 tM Series DIO User Manual Rev A1 3 7PH 013 A13 12 7 495 109 02 08 sales bbrc ru www bbrc ru...
Страница 13: ...tM R5 tM Series DIO User Manual Rev A1 3 7PH 013 A13 13 7 495 109 02 08 sales bbrc ru www bbrc ru...
Страница 22: ...1 5 Dimensions tM Series DIO User Manual Rev A1 3 7PH 013 A13 22 7 495 109 02 08 sales bbrc ru www bbrc ru...