Location of Ice Machine
The location selected for the ice machine must meet
the following criteria. If any of these criteria are not
met, select another location.
•
The location must be free of airborne and other
contaminants.
•
Self contained air and water cooled - The air
temperature must be at least 50°F (10°C), but must
not exceed 100°F (37°C).
•
Self contained air, water cooled, remote air cooled -
The pottable water temperature must be at least 50°
F (10°C), but must not exceed 90°F (32°C).
•
Remote air cooled - The air temperature must be at
least -20°F (-29°C), but must not exceed 120°F (49°C)
•
Ice Making Water Inlet - Water Pressure must be at
least 20 psi (1.38 bar), but must not exceed 80 psi
(5.52 bar).
•
Condenser Water Inlet - Water Pressure must be at
least 20 psi (1.38 bar), but must not exceed 150 psi
(10.34 bar).
•
Condenser Water Inlet - Water Temperature must be
at least 50°F (10°C), but must not exceed 90°F (32°C).
•
The location must not be near heat-generating
equipment or in direct sunlight and protected from
weather.
•
The location must not obstruct air flow through or
around the ice machine. Refer to chart below for
clearance requirements.
Clearance Requirements
AIR, WATER, REMOTE CONDENSER MODELS
IM0350, IM0460
IM0550, IM0680
IM0770, IM1100
Self-Contained
Air-Cooled
Water-Cooled
and Remote
Top
12" (30.4 cm)
12" (30.4 cm)
Sides & Back
8" (20.3cm)
8" (20.3cm)
20
Содержание IM Series
Страница 1: ...Revision Date 1 24 22 IM Series Air Water Remote Ice Machines Technician s Handbook ...
Страница 2: ......
Страница 3: ...THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 9: ...THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 15: ...THIS PAGE INTENTIONALLY LEFT BLANK 14 ...
Страница 17: ...How to Read a Serial Number Full Serial Number 16 ...
Страница 35: ...THIS PAGE INTENTIONALL Y LEFT BLANK 34 ...
Страница 48: ...Flexible Numeric Display FND Functions 47 ...
Страница 93: ...THIS PAGE INTENTIONALLY LEFT BLANK 92 ...
Страница 106: ...Testing the water level sensor Before S N Starting With VC 105 ...
Страница 134: ...SERVICE REMOTE RECOVERY EVACUATION CONNECTIONS 133 ...
Страница 145: ...THIS PAGE INTENTIONALLY LEFT BLANK 144 ...
Страница 154: ...IM1100 SERIES IM1100R Remote Air Cooled Model Characteristics vary depending on operating conditions CYCLE TIMES 153 ...
Страница 155: ...THIS PAGE INTENTIONALLY LEFT BLANK 154 ...
Страница 157: ...Wiring Diagram 156 ...
Страница 158: ...PCB Layout 157 ...
Страница 159: ...PCB Dip Switches 158 ...
Страница 161: ...SPACE FOR TECHNICIAN S NOTES ...
Страница 162: ...SPACE FOR TECHNICIAN S NOTES ...
Страница 163: ...SPACE FOR TECHNICIAN S NOTES ...
Страница 164: ...SPACE FOR TECHNICIAN S NOTES ...
Страница 165: ......