DIAGNOSING START COMPONENTS
If the compressor attempts to start, or hums and trips the
overload protector, check the start components before
replacing the compressor.
Capacitor
Visual evidence of capacitor failure can include a bulged
terminal end or a ruptured membrane. Do not assume a
capacitor is good if no visual evidence is present. A good
test is to install a known good substitute capacitor. Use a
capacitor tester when checking a suspect capacitor. Clip
the bleed resistor off the capacitor terminals before
testing.
Relay
The relay has a set of contacts that connect and
disconnect the start capacitor from the compressor start
winding. The contacts on the relay are normally closed
(start capacitor in series with the start winding). The relay
senses the voltage generated by the start winding and
opens the contacts as the compressor motor starts. The
contacts remain open until the compressor is de-
energized.
RELAY OPERATION CHECK
1. Disconnect wires from relay terminals.
2. Verify the contacts are closed.
Measure the resistance between terminals 1 and
2. No continuity indicates open contacts. Replace
the relay.
3. Check the relay coil.
Measure the resistance between terminals 2 and
5. No resistance indicates an open coil. Replace
the relay.
117
Содержание IM Series
Страница 1: ...Revision Date 1 24 22 IM Series Air Water Remote Ice Machines Technician s Handbook ...
Страница 2: ......
Страница 3: ...THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 9: ...THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 15: ...THIS PAGE INTENTIONALLY LEFT BLANK 14 ...
Страница 17: ...How to Read a Serial Number Full Serial Number 16 ...
Страница 35: ...THIS PAGE INTENTIONALL Y LEFT BLANK 34 ...
Страница 48: ...Flexible Numeric Display FND Functions 47 ...
Страница 93: ...THIS PAGE INTENTIONALLY LEFT BLANK 92 ...
Страница 106: ...Testing the water level sensor Before S N Starting With VC 105 ...
Страница 134: ...SERVICE REMOTE RECOVERY EVACUATION CONNECTIONS 133 ...
Страница 145: ...THIS PAGE INTENTIONALLY LEFT BLANK 144 ...
Страница 154: ...IM1100 SERIES IM1100R Remote Air Cooled Model Characteristics vary depending on operating conditions CYCLE TIMES 153 ...
Страница 155: ...THIS PAGE INTENTIONALLY LEFT BLANK 154 ...
Страница 157: ...Wiring Diagram 156 ...
Страница 158: ...PCB Layout 157 ...
Страница 159: ...PCB Dip Switches 158 ...
Страница 161: ...SPACE FOR TECHNICIAN S NOTES ...
Страница 162: ...SPACE FOR TECHNICIAN S NOTES ...
Страница 163: ...SPACE FOR TECHNICIAN S NOTES ...
Страница 164: ...SPACE FOR TECHNICIAN S NOTES ...
Страница 165: ......