Self-Contained Recovery/Evacuation
1. Use the 'ICE/OFF/WASH' switch to turn the ice
machine off.
2. Install manifold gauges, scale and recovery unit
or two-stage vacuum pump and open high and
low side on manifold gauges.
MANIFOLD SET
OPEN
VACUUM PUMP/
RECOVERY UNIT
CLOSED
OPEN
LOW SIDE
ACCESS
VALVE
HIGH SIDE
ACCESS
VALVE
OPEN
RECOVERY/EVACUATION CONNECTIONS
3. Perform recovery or evacuation:
A. Recovery: Operate the recovery unit as
directed by the manufacturer’s instructions.
B. Evacuation prior to recharging: Pull the system
down to 500 microns. Turn off the pump and
perform a standing vacuum leak check to
ensure the micron level does not rise beyond
1,000 microns within 5 minutes.
4. Follow the Charging Procedures.
127
Содержание IM Series
Страница 1: ...Revision Date 1 24 22 IM Series Air Water Remote Ice Machines Technician s Handbook ...
Страница 2: ......
Страница 3: ...THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 9: ...THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 15: ...THIS PAGE INTENTIONALLY LEFT BLANK 14 ...
Страница 17: ...How to Read a Serial Number Full Serial Number 16 ...
Страница 35: ...THIS PAGE INTENTIONALL Y LEFT BLANK 34 ...
Страница 48: ...Flexible Numeric Display FND Functions 47 ...
Страница 93: ...THIS PAGE INTENTIONALLY LEFT BLANK 92 ...
Страница 106: ...Testing the water level sensor Before S N Starting With VC 105 ...
Страница 134: ...SERVICE REMOTE RECOVERY EVACUATION CONNECTIONS 133 ...
Страница 145: ...THIS PAGE INTENTIONALLY LEFT BLANK 144 ...
Страница 154: ...IM1100 SERIES IM1100R Remote Air Cooled Model Characteristics vary depending on operating conditions CYCLE TIMES 153 ...
Страница 155: ...THIS PAGE INTENTIONALLY LEFT BLANK 154 ...
Страница 157: ...Wiring Diagram 156 ...
Страница 158: ...PCB Layout 157 ...
Страница 159: ...PCB Dip Switches 158 ...
Страница 161: ...SPACE FOR TECHNICIAN S NOTES ...
Страница 162: ...SPACE FOR TECHNICIAN S NOTES ...
Страница 163: ...SPACE FOR TECHNICIAN S NOTES ...
Страница 164: ...SPACE FOR TECHNICIAN S NOTES ...
Страница 165: ......