ibis SiViB Record 1500 Скачать руководство пользователя страница 6

IBIS

 GmbH           

SiViB 

Record 1500 / Record Control Manual                    

      

 Page 6

 

 

IBIS

 Ingenieurbüro für Instandhaltungs- und Schwingungsmeß-Systeme GmbH 

Reinheimer Str. 17, 64846 Groß-Zimmern, Germany; www.ibis-gmbh.de 

Tel. +49 6071/42222, Fax +49 6071/71707, Email: [email protected]

 

8: Alarm set input. Opto coupler input for 24 V DC signal from machine control system. Can be used to 
monitor two different operation conditions of the machine requiring different alarm level setpoints. Input 
= 1 (high) activates alarms set 1. If the terminal is not connected, alarms set 0 is always active. 
9: Machine speed input. Opto coupler input for 24 V signal once per rev. Standard inductive non 
contacting pickups can be connected directly. Use terminal 11 as ground for this signal. 
10: Supply for alarm o24 V DC. Necessary for opto coupler outputs. Should be taken from the 
supply of the connected machine control system.  
11: Ground alarms. Should be taken from the supply of the connected machine control system. 
12: Analog output 0 – 10 Volts for mm/s overall of input 1. Use terminal 2 or 4 for ground. 
13: Analog output 0 – 10 Volts for gSE overall of input 1. Use terminal 2 or 4 for ground. 
14 – 15 Ground for analogue outputs 
16: Analogue input 1 
17: Analogue input 1 ground 
18: Analogue input 2 
19: Analogue input 2 ground 
20: Analogue input 3; for 2 channel SiViB 1502 accelerometer 2 signal (like terminal 3) 
21: Analogue input 3 ground; for 2 channel SiViB 1502 accelerometer 2 ground (like terminal 4) 
22: SiViB 1501 and 1511: Analogue input 4;  
      SiViB 1502 and 1512  Analog output 0 – 10 Volts for mm/s overall of input 2 
23: SiViB 1501 and 1511:Analogue input 4 
 … . SiViB 1502 and 1512  Analog output 0 – 10 Volts for gSE overall of input 2 
 

Attention: 

The analogue inputs are preconfigured according to your order for 0 – 10 V DC or 

temperature sensors type PT1000, KTY84 or VT. These hardware configuration can not be changed 
by the end user. Please refer to the nameplate of the instrument, which states the configuration.  
 
24 to 26: Digital inputs DigIn 1 to 3, opto coupler 24 V DC inputs for connection to PLC outputs. The 
status of these inputs get recorded with every other storage of vibration data. 
 
DigIn 1 can get configured as “Event enable”. If this is set, Events will only get stored if DigIn4 = high. 
DigIn2 can be used as counter for operating hours 
DigIn3 can be used as counter for tool change operations 
 
27: Digital input „store“. A 24 V high signal causes the storage of a data set.  
28: Digital Ground for digital inputs 
29: Reserved for option CAN bus Ser+ 
30: Reserved for option CAN bus Ser- 
 

Earting and Grounding:

 Depending on the earth situation it might be necessary to ground the 

instrument using one of the analog ground terminals (e.g. 4,17,19, 21). Please take care to use a 
“clean” earth carrying no leakage currents or other signals, as those would be seen as noise signals 
on the instruments inputs. 
If the earth is heavily contaminated, it might be better to keep the monitor ungrounded and the sensor 
cable shield connected to signal ground only (terminal 4).  
 
Where to mount the instrument: Choose a place for mounting the instrument, which is as away from 
sources of electrical noise. Motor drives, unshielded power cables or inductive transformers could be 
such sources, which should be avoided. 
 
 

Содержание SiViB Record 1500

Страница 1: ...SiViB Record 1500 SiViB Record Control Installation Instructions and Operation Manual Version 3 1 2012...

Страница 2: ...CONFIGURATION 13 Software Language and Data Path 13 Communication 13 Setup Procedure for SiViB Record 1500E 14 Online Record Control Net only 17 CONFIGURATION AND COMMISSIONING 19 NEW INSTRUMENT 19 IN...

Страница 3: ...071 71707 Email info ibis gmbh de Drag Tool 43 Zoom Tool 44 Cursor Movement 44 Cursor Curve Selection 44 Graph Colors 45 RECORD CONTROL NET 46 Overview Table 47 Setting Update Rate and Time 48 Mail on...

Страница 4: ...he according output will switch to alarm If meaningful an input controlling the active set of alarm setpoints can be used The machine control system can provide the information if the machine is in id...

Страница 5: ...15 Ground for analog outputs 16 1st upper row AIN 1 analogue input 1 17 Analog GND 18 AIN 2 19 Analog GND 20 AIN 3 or accelerometer 2 signal 21 Analog GND or accelerometer 2 ground 22 1501 1511 AIN4...

Страница 6: ...output 0 10 Volts for mm s overall of input 2 23 SiViB 1501 and 1511 Analogue input 4 SiViB 1502 and 1512 Analog output 0 10 Volts for gSE overall of input 2 Attention The analogue inputs are preconf...

Страница 7: ...e per rev 10 24 V DC Supply for alarm outputs 11 Ground alarms 12 Option Analog Out 0 10 Volt for mm s for input 1 13 Option Analog Out 0 10 Volt for gSE for input 1 14 Ground for analog outputs 15 Gr...

Страница 8: ...11 Ground alarms 12 Option Analog Out 0 10 Volt for mm s for input 1 13 Option Analog Out 0 10 Volt for gSE for input 1 14 Ground for analog outputs 15 Ground for analog outputs 16 1st upper row Optio...

Страница 9: ...urrent probes 20 Supply for eddy current probes 24Volts max 40 mA 21 ECP1 Analog output 0 10 Volts DC for position 22 ECP1 Analog output 0 10 Volts DC for vibration 23 Out Ground for analog outputs 24...

Страница 10: ...n 800 x 600 256 colors Operating System SiViB Record Control runs under Windows 98 XP Vista Win7 Installing the Software Put the CD into your CD ROM drive Click Start Run Type D English setup if your...

Страница 11: ...card reader connector The driver of the card reader will find the reader automatically so you do not need to set the port manually There are other types of card readers with only the COM Port connecto...

Страница 12: ...e the Quit button or the Escape key of your keyboard Avoid leaving windows open when jumping back Otherwise windows in the background might stay active and the software appears blocked or misbehaving...

Страница 13: ...e required one and change the setting Choose the bus system first RS232 Choose the COM port to use with a serial null modem cross over cable for communication betreen instrument and PC The baudrate is...

Страница 14: ...B The factory default IP adress is 192 168 42 50 Subnet Mask 255 255 255 0 For the PC you can use any free IP adress in the same range e g 192 168 42 1 Open your web browser and type the factory defau...

Страница 15: ...serial RS232 communication The status line at the bottom of the main window shows the selected COM Port number Go to the Setup Window Click Read Setup from Instrument Allow the system 3 5 seconds to...

Страница 16: ...System Options from Main Window Tab Communication Select Multi Bus System click Store Settings Password is sivib Close Record Control and reopen it This makes the changes in system options active Ple...

Страница 17: ...larm set to use for the overview table Delete data in instrument after unload Deletes the data memory of the instrument after automatic unload If you are using email on alarm this avoids repeated alar...

Страница 18: ...ption in live mode Logfile for communication If set to write logfile all communication telegrams sent between instrument and PC get logged to a file Attention The log file will get very large if you k...

Страница 19: ...new SiViB connect the instrument to your PC using a null modem cable Connect the 24 Volts power supply and switch it on Boot your PC and start Record Control From main window select New Instrument Fil...

Страница 20: ...nstrument and set the input configuration accordingly SiViB 1502 and 1512 both have a second input for an accelerometer Set line 3 for vibration mm s and line 4 for bearing condition gSE On these type...

Страница 21: ...ctivation of event storage Set all inputs to active which should trigger events The button Event recording alwas on or Event recording only if DigIn1 high allows you to make event recording dependant...

Страница 22: ...nsitivity Pickup sensitivity 100 coresponds to the standard input sensitivity of the input Use this for correction of sensitivity deviations of the particular sensor connected Example A particular sen...

Страница 23: ...nd the correct sensitivity and offset values Calibration procedure Move the sensor to the near calibration point close to the target recommended 100 to 200 ADUs current value Measure the mechanical di...

Страница 24: ...watis for interval time before the first data set is stored Then it stroes after each time interval as long as the speed window is true Interval FFT The settings for Interval Spectrum are only releva...

Страница 25: ...will replace the current settings in the upper part of the window 4 Click Store changes to make the settings valid Send Setup to SiViB Important Store the settings by clicking Store Settings before yo...

Страница 26: ...t to the instrument using a null modem cable Click Setup Set instrument date time The window shows both date and time from the PC and the instrument Click Send data time to instrument for synchronizin...

Страница 27: ...ecord Control software In the main screen click Read Trend Data serial Watch the status bar at the bottom of the screen for messages telling you the progress of the data transfer Record Control checks...

Страница 28: ...ail info ibis gmbh de Back at your PC click Memory Card in the main screen and Read data from card Wait until the status line says insert card please Plug the card into the reader with the golden cont...

Страница 29: ...tion drop down box The serial number shown on the instrument s nameplate just the number without any slashes or letters other then numbers will then be shown in the serial number display box You can f...

Страница 30: ...uploaded The switch Graph activates or deactivates the chart On slow PCs this can be useful when writing to file When a signal is higher then the measurement range a red over indicator will replace th...

Страница 31: ...logfiles and set the switch timestamp in live files to seconds since 1904 Converting seconds since 1904 to time and date string If you want to use the live data files with a spread sheet software e g...

Страница 32: ...ou have selected more then one instrument the table will have additionnal colons for the values Refer to the descrepion above for more details of the file format The advantage of the Log to file funct...

Страница 33: ...ph The trend graph is useful for looking at longer term changes in the values maybe pointing at deterioration of the machine Trend graphs are based on data taken regularly under comparable conditions...

Страница 34: ...Click Store Changes and type your password Store Trend Data to TXT File If you want to process the trend data using other software you can transfer the data records from the instruments trend data me...

Страница 35: ...gger and the remaining 96 after the trigger This allows to see the behavior of the values right before and after the event happened Event triggering The event data sets described above will be stored...

Страница 36: ...e following table Digital Inputs Byte Bit 7 6 5 4 3 2 1 0 _____ Alarm Set ___________ not used _________________ not used _______________________ not used _____________________________ DigIn1 ________...

Страница 37: ...can be reset to 0 Tool Cange Counter SiViB Record has a tool change counter For each tool change a pulse of minimum 200 ms duration hast to be set on digital input 3 terminal 26 SiViB Record counts t...

Страница 38: ...ed firmware 2 9 and Record Control Software Version 3 0 14 or higher The window type Bargraf shows all values of one instrument in a bargraf or tank type format The bars change colors according to the...

Страница 39: ...software shows the time waveform and the FFT spectrum as soon as the transfer is completed The next measurement is then started automatically The button Measurement running Measurement stopped allows...

Страница 40: ...nits 1501 1511 Input accelerometer v RMS mm s 1502 1512 Input accelerometer 1 and 2 v RMS mm s 1503 1513 1603 Input accelerometer 1 2 and 3 v RMS mm s 1532 Input eddy current probe 1 and 2 and acceler...

Страница 41: ...to use the date for further examination using other programs e g Excel Any text typed in the field Comments is being stored at the beginning of the ASCII file Name and path of the file can be entered...

Страница 42: ...perpendicular to each other A machine speed reference signal one pulse per rev You must use a serial connection between instrument and PC The orbit function samples the input signals from both inputs...

Страница 43: ...ctical setting If however you want to zoom in to a specific part of the graph you must turn off auto scaling If the sliding switch is turned to right see picture autoscaling is on Click on the switch...

Страница 44: ...ection window Move the cursor it the drawing area and drag a rubber band rectangle by holding the left mouse button When you release the mouse button the area inside the rectangular will zoom in The e...

Страница 45: ...n be placed everywhere Digital display shows cursor position Snap to point or curve Cursor moves only from point to point along the curve Selection of the curve Graph Colors If you click on a line of...

Страница 46: ...must have the CAN Bus option or an RS232 to Ethernet bridge fitted In a networked system all SiViB instruments are working independently and in the same manner as in a stand alone configuration Only...

Страница 47: ...t points Besides the numeric value the color of the fields indicate the alarm state as follows Green O K Yellow Alarm 1 Red Alarm 2 Blue Event Alarm Grey Point inactive The overview table gets update...

Страница 48: ...the software checkes for alarm conditions and creates a alarm message file These file is sent to all mail addresses set in the file Dat mailadresses txt You can open and modify this file using a word...

Страница 49: ...CAN ID to a number between 1 an 255 unique for each instrument The CAN Baudrate must be the same for all instruments on the same Bus cable 125kBps is a good choice for cables of up to 400 m length Ple...

Страница 50: ...to the gateway using the RS232 conectors and a nullmodem cable Start Hyperterminal by double clicking Eth_CAN ht ind the record control folder You will get a message like this Welcome at SYSTEC CAN E...

Страница 51: ...plate mounting Dimensions 100 x 75 x 110 mm WxHxD Inputs Outputs 30 screw terminals 1 or 2 inputs for accelerometers ICP supply sensitivity 10 100 or 500 mV g 4 or 2 inputs for DC Volts 0 10 Volts or...

Страница 52: ...eter 100 mV g 2 inputs for eddy current probes 8 mV m SiV01 032 SiViB Record Control Light Configuration software for Windows free with instrument SiV09 030 SiViB Record Control Pro For configuration...

Страница 53: ...The Record Control Software uses drivers for the card reader which are instrument specific Therefore it is not possible to use other card readers presently Question On my SiViB the red LED Card Error...

Отзывы: