Manual
ibaMS4xUCO
54
Issue 1.5
Electrical isolation
Channel-24Volt ground
Channel-channel/housing
AC 1.5 kV
AC 1.0 kV
Connector type
1x37-pin Sub-D connector, soldered terminal (0.8 mm
2
to
1.2 mm
2
), can be connected by screws, included in delivery
10.3
Digital inputs
Number
8
Design
Galvanically isolated, single ended, protected against re-
verse polarity
Input signal
24 V DC
Max. input voltage
±60 V permanent
Signal level log. 0
Signal level log. 1
Hysteresis
> -6 V; < +6 V
< -10 V; > +10 V
none
Input current
1 mA, constant
Debounce filter
Optional: 4 different operating modes
Sampling rate
Up to 40 kHz, freely adjustable
Frequency range
0 Hz to 20 kHz
Delay
Typ. 10 μs
Electrical isolation
Channel
– channel
Channel
– housing/power supply
AC 2.5 kV
AC 2.5 kV
Connector type
1 x 16-pin multi-pin connector, clamp-type terminal
(0.8 mm
2
to 2.5 mm
2
), screw connection, included in deliv-
ery
10.4
Digital outputs
Number
4
Design
1 root with 4 outputs, P switch
Load voltage
24 V DC, external per root, protected against reverse polar-
ity
Load voltage range
+10 V to +30 V
Switching voltage per channel
= load voltage
Switching current per channel
250 mA
Switching current range per channel
10 mA to 500 mA
Inductive load
Up to 200 mJ
Switching frequency
Up to 40 kHz
5
, freely adjustable
Switching delay
Switch-on delay (90% to 10%)
Switch-off delay (10% to 90%)
< 10
μs
< 10 µs at 24 V DC switching voltage with 100
Ω load
5
deviating switching frequency with ibaLogic (up to 1 kHz) and ibaPDA (up to 20 Hz)