11.2.1
The first Test
11.2.1.1 SIMATIC S7 Application unidirectional (S7- 300)
An analog value (e.g. a temperature scaled with FC105 from S7 standard library) is to
be transferred as a REAL-variable from S7-PLC to ibaBM-DPM-S-64.
Figure 13:
Connection between ibaBM-DPM-S-64 and ibaPDA
Step 1: FO connecting and cabling
Because ibaPDA is a passive application and thus only reads data from the Profibus,
the modes 0, 1 and 3 are available.
1.
Connect the fiber optical transmitting link (TX) on the ibaBM-DPM-S-64 with a re-
ceiving link on the FOB-card in the ibaPDA-PC.
2.
Start the ibaPDA-software and define 2 SM64-
modules in the “Module selection”
menu o
f ibaPDA v 5.x or a module “DPM64” in the IO manager of ibaPDA-V6 re-
spectively.
3.
Start the diagnostics tool in ibaPDA v 5.x (<F12>) and select a SM64- module of the
FOB-card in the tree structure. In ibaPDA-V6 mark in the IO manager the corre-
sponding link under the FOB card in the signal tree.
Without being connected to the Profibus line, the ibaBM-DPM-S-64 should send
valid messages to ibaPDA. Using the diagnostics of ibaPDA or the software ibaDiag
you should be able to watch the message counter running.
As soon as the connection between the DP master and both slaves of ibaBM-DPM-
S-64 has been established the
“Bus” LED should light yellow and the “Act” LED
white.
Step 2: GSD file installation and hardware configuration
1.
Start the “HW Config” tool in the current S7-project and install the GSD-file named
“ibaF04n3.gsd “.
2.
In the web interface of the ibaBM-DPM-S-64 set the operation mode to mode 3
(PDA 28 Reals).
3.
Open the “Profibus DP”- folder in the hardware catalog of "HW Config".