7.3.4
Operating Status Display (Status LEDs)
LED
Status
Description
Run
(green)
Blinking
(approx. 1 Hz)
On or off
Device is working; irregular blinking rate indicates device
is overloaded
Controller ok, device has "crashed"
3Mb
(yellow)
Off
blinking
On
No communication 3 Mbit/s to TX
Data transfer rate 3 Mbit/s (send only)
Data transfer rate 3 Mbit/s (send and receive)
32Mb (white) On
Off
-
-
Stop (red)
Off
blinking
On
Normal, everything Okay
Defect (error while booting)
Error, device-internal applications not running
7.3.5
24 V Power Supply
The ibaBM-DPM-S-64 device requires an external DC 24 V power supply (unregulated)
and should be operated at a maximum of 600 mA. The operating voltage should be run
through the provided 2-pin Phoenix threaded coupling connector. If desired, you can
order DIN rails or plug-in power supply units from iba.
7.3.6
Status LEDs of the Communications Interface
LED
Status
Description
CF
Off
Green
Red
No CF card inserted
Card detected (card may also be empty), driver loaded;
LED flickers during data transfer
Error CF card, e.g. incorrect card type or start-up phase
Ethernet
Off
Green
Red
Ethernet cable not connected
Driver loaded, LAN ready; LED flickers during data transfer
Defect; driver not loaded
USB
Off
Green
Red
Normal if nothing is connected
Connected device detected, driver loaded, LED flickers dur-
ing data transfer
Defect or communication setup
7.3.7
Switches S1 and S2
The rotary switches are used to reset the device to default settings. In contrast to the
predecessor ibaBM-DPM-64 the address setting is done via software not by rotary
switches.
For more information see chapter