Manual
ibaBM-DPM-S-64
12
Issue 2.5
6
Mounting and dismounting
6.1
Mounting
1.
Locate the DIN rail mounting clip on the rear side of the device. Place the device on
the DIN rail so that the top part of the mounting clip engages the top part of the rail
appropriately. Slowly push down and in so that the bottom part of the mounting clips
snaps onto the bottom part of the rail and firmly fixes the device to the DIN rail.
2.
If there is a rule to ground the device, connect the device to the ground (shield con-
nector X29).
3.
Once fixed, connect the DC 24 V power supply to the termination shown on the de-
vice. Ensure that the polarity is correct prior to applying power. Then install the oth-
er connections like:
Connecting the Profibus cable
The PROFIBUS cable should be connected after proper completion of the active slave
configuration only to ensure that the slave numbers do not exist twice. A conflict due to
slaves with the same number can lead to a breakdown of the Profibus communication
and finally to a complete standstill of the system.
4.
Connect the FO cable and if needed, activate the Profibus terminating resistor with
switch S4 or S5.
6.2
Dismounting
1.
Disconnect all external connections from the device.
2.
Grasp the device with one hand firmly on the top side. With your free hand, grasp
the bottom of the device so that your index and pointer fingers rest on the ground-
ing screw.
3.
Lightly push down with the hand on the top side of the device and simultaneously
pull forward with your other hand. With this action, the device should free itself from
the DIN rail.