ibaBM-DPM-S-64
Manual
Issue 2.5
25
9.2.1
Modes of Operation Overview
The following table gives an overview about the modes of operation which are available
on the device. For each mode you’ll find the appropriate GSD files in the corresponding
row which should be installed on the DP master. For more information please refer to
the following chapters.
Mode Name
Outputs
Inputs
GSD-file
Application
0
PDA 32 Integers
2 * 32 analog (int)
2 * 32 digital
-
ibaF01n4.gsd
ibaF01n3.gsd
iba_0F01.gsd
ibaPDA, ibaLogic,
SIMATIC S7
system coupling
1*
PDA 32 Reals
2 * 32 analog (real)
2 * 32 digital
-
iba_0F02.gsd
ibaPDA, ibaLogic,
system coupling
no S7, SD
2
n/a
-
-
-
-
3
PDA 28 Reals
2 * 28 analog (real)
2 * 32 digital
-
ibaF04n4.gsd
ibaF04n3.gsd
iba_0F04.gsd
ibaPDA, ibaLogic,
S7,
system coupling
4
n/a
-
-
-
5
INPUT 32 Integers
(4 byte reserved)
2 * 32 analog (int)
2 * 32 digital
ibaF00n4.gsd
ibaF00n3.gsd
ibaLogic, S7,
system coupling
6*
INPUT 32 Reals
(4 byte reserved)
2 * 32 analog (real)
2 * 32 digital
iba_0F06.gsd
ibaLogic,
system coupling
no S7, SD
7
INPUT 28 Reals
(4 byte reserved)
2 * 28 analog (real)
2 * 32 digital
ibaF07n4.gsd
ibaF07n3.gsd
ibaLogic, S7,
system coupling
8
IN-OUT 32 Integers 2 * 32 analog (int)
2 * 32 digital
2 * 32 analog (int)
2 * 32 digital
ibaF08n4.gsd
ibaF08n3.gsd
iba_0F08.gsd
ibaLogic, S7,
system coupling
9*
IN-OUT 32 Reals
2 * 32 analog (real)
2 * 32 digital
2 * 32 analog (real)
2 * 32 digital
iba_0F09.gsd
ibaLogic,
system coupling
no S7, SD
A
n/a
-
-
-
-
B
IN-OUT 28 Reals
2 * 28 analog (real)
2 * 32 digital
2 * 28 analog (real)
2 * 32 digital
ibaF0Bn4.gsd
ibaF0Bn3.gsd
ibaLogic, S7
system coupling
* Not applicable to former CPUs SIMATIC S7 (firmware <2.0 for S7-300, firmware < 3.0 for
S7-400) or SIMADYN D
Note
Please note that the terms "in" and "out" refer to the point of the Profibus master
’s
view, i.e. "in" means signals being transmitted from the ibaBM-DPM-S-64 to the Profi-
bus master (e. g. SIMATIC S7), "out" vice versa.
Both slaves are always set to the same mode for the analog values!