ibaBM-DPM-S-64
Manual
Issue 2.5
51
11
Applications
11.1
General application
1.
Install or copy the appropriate GSD file(s) on the Profibus master. The choice of
GSD-file depends on the mode to be used.
For more information see chapter „Modes of Operation and Data Types “, page 24.
2.
By means of the master configuration program register the GSD-file(s) in order to
assign the ibaBM-DPM-S-64 slaves.
3.
Connect the ibaBM-DPM-S-64 physically with the DP line.
Connecting the Profibus cable
The PROFIBUS cable should be connected after proper completion of the active slave
configuration only to ensure that the slave numbers do not exist twice. A conflict due
to slaves with the same number can lead to a breakdown of the Profibus communica-
tion and finally to a complete standstill of the system.
4.
Activate application-specific transfer programs in the master.
5.
Connect the fiber optical links of the ibaBM-DPM-S-64 with the other application,
e. g. ibaPDA, ibaLogic etc.
11.2
Applications with SIMATIC S7
In the following sections you will find a description of 2 very simple applications for uni-
and for bidirectional communication with ibaBM-DPM-S-64 which show the principles in
configuration and engineering.
The following remarks concerning applications with SIMATIC S7 basically apply also to
SIMATIC TDC and SIMADYN D accordingly.