![IAI RCM-TD Скачать руководство пользователя страница 90](http://html1.mh-extra.com/html/iai/rcm-td/rcm-td_operating-manual_3308997090.webp)
82
Caution:
Caution: Do not input any numeric value other than 1, 2, 3, 4, 90, 91, 92, 93, and 5119 into
Adjust No.
In the case of the RCP or RCP2 controller, 0 or 2 is set to parameter No. 25 (PIO pattern)
(when there is no servo ON input), do not input 92 into Adjust No., either. The controller will be
inoperable due to no servo ON input.
- If you input 1 into Adjust No. and press the
Return key, homing will be performed.
- Temporary stop effect: 90
Input 90 into Adjust No. and press the Return
key.
After that, turn off the controller power.
- Temporary stop non-effect: 91
Input 91 into Adjust no. and press the Return key.
After that, turn off the controller power.
- Servo ON input effect: 92
Input 92 into Adjust no. and press the Return key.
After that, turn off the controller power.
- Servo ON input non-effect: 93
Input 93 into Adjust No. and press the Return
key.
After that, turn off the controller power.
- Axis number setting
Move the cursor to Adjust No. with the key.
Input the axis number and press the Return key.
Input 2 into Adjust No. and press the Return key.
After that, turn off the controller power.
* In the case of the PCON-C/CG and other
controllers for which the axis number is set with
the rotary switch on the front panel of the
controller, axis number setting is not available.
Содержание RCM-TD
Страница 1: ...Teaching Pendant Operating Manual First edition IAI America Inc...
Страница 2: ......
Страница 4: ......
Страница 6: ...MEMO...
Страница 14: ...6 6 2 External View External Dimensions When drawing out the manual card...
Страница 82: ...74 Pulse Position Display PCON PL PO ACON PL PO SCON Pulse Train Mode Current Value mA Display 1 6 5...
Страница 86: ...78 Examples of PCON CY Controller...
Страница 105: ......