Engine-driven generator recommendations
Generators used with the Powermax65 or Powermax85 should satisfy the following requirements:
CSA
• 1-phase, 50/60 Hz, 230/240 VAC
• 3-phase, 50/60 Hz, 200-600 VAC (480 VAC recommended for best performance)
CE
• 3-phase, 50/60 Hz, 380/400 VAC (400 VAC recommended for best performance)
Note: Based on the generator rating, age, and condition, adjust the cutting current as needed.
If a fault occurs while using a generator, turning the power switch quickly to OFF and then to ON again
(sometimes called a “quick reset”) may not clear the fault. Instead, turn OFF the power supply and wait 30 to
45 seconds before turning ON again.
Engine drive
rating
System output
current
Performance
(arc stretch)
20 kw
85 A
Full
15 kw
70 A
Limited
15 kw
65 A
Full
12 kw
65 A
Limited
12 kw
40 A
Full
8 kw
40 A
Limited
8 kw
30 A
Full