IP Relay HWg-ER02b - Manual
HW group
www.HW-group.com
13/ 42
Setting up without WWW (TCP Setup)
Use the Hercules utility:
Change to the “
TCP Client
” tab and enter the configured IP address. Set the
TCP port
to
99
.
Click “Connect”. The listing on the left displays the “
WEB51>
” prompt. Click inside this pane
and press ENTER. The window displays the current configuration.
To set a parameter, enter the
corresponding letter and the desired
value (for example “
I192.168.6.8
” to
set the device IP address). To
show the help for a command, enter
the command and a question mark,
and press ENTER
– for example,
“
I? <Enter>
“. All the settings are
described in detail later in this
manual.
After setting the parameters, use R
for
Reboot
and press “Disconnect”
to disconnect from the device. The
device restarts.
Note:
TCP Setup can be disabled
with the “Enable TCP setup” option.
When unchecked, the device
refuses connections to port 99.
Setting up the device using a RS-232 terminal
If you do not have Windows or our Hercules utility available, you can set up the device over RS-232
using any terminal.
Set
DIP1 = ON
,
DIP2 = OFF.
Connect RS-232 (port 1) to a PC using the
supplied
LapLink
cable.
Open your favorite terminal program (e.g.
Hyperterminal), choose the correct serial
port and configure it to
9600 8N1
.
Connect the power adapter to the
electrical outlet and to the device.
If the power is OK, the green
Power
LED
should light up.
If the serial cable and terminal program
are working, the text menu for configuring
the device appears.
Continue by following the steps as in the previous
case.