CIM800 Contact Input Module – Installation Instructions
MZX CIM800
Installation Instructions Doc. version 4.0
1/8
CIM800 Contact Input Module – Installation
Instructions
Technical specification
Electromagnetic Compatibility
The CIM800 complies with the following:
Product family standard EN 50130-4 in
respect of Conducted Disturbances, Radiated
Immunity, Electrostatic Discharge, Fast Tran-
sients and Slow High Energy
EN 61000-6-3 for emissions
Introduction
The CIM800 Contact Input Module is designed
to monitor fire contacts such as extinguishing
system control, ventilation control, fire door con-
trol etc. The CIM800 can be configured as:
Two spur circuits (Class B) monitoring multi-
ple normally open contacts, with short circuit
giving a fault output.
Fig. 1: CIM800 Contact Input Module
Parameter
Value
Type Identification
Value:
145
System Compatibility:
Use only with MX
Fire Alarm Control-
lers
Environment:
Indoor Application
only
Operating Temperature:
-25 °C to +70 °C
Storage Temperature:
-40 °C to +80 °C
Operating Humidity:
Up to 95 % non-
condensing
Dimensions (HWD):
87 x 148 x 14 mm
Weight:
100 g
Mounting Require-
ments:
One MK backbox
surface mount or an
ANC-8 ancillary
housing
Table 1: Technical Specifications
Battery Requirements:
Standby current:
Alarm current:
0.505mA
4.5mA
Wire Size:
Min 1.5 mm
2
Max 2.5 mm
2
Maximum Wiring
Resistance Monitored
Circuit:
10 ohm
Addressable Device
Conditions:
Normal
Active
Short Circuit wir-
ing fault
Open Circuit
wiring fault
Device Type
Invalid
Device No
Response
Parameter
Value
Table 1: Technical Specifications