Installation Instructions  Doc. version 4.0

MZX CIM800

MZX Fire detection system

Two spur circuits (Class B) monitoring single 
normally closed contacts, with short circuit 
giving a fault output.

Single loop circuit (Class A) monitoring a nor-
mally open contact, with short circuit giving a 
fault output.

Single loop circuit (Class A) monitoring a nor-
mally closed contact, with short circuit giving 
a fault output.

Two spur circuits (Class B) monitoring multi-
ple normally open contacts, with short circuit 
giving an alarm.

Single loop circuit (Class A) monitoring multi-
ple normally open contacts, with short circuit 
giving an alarm.

Features

The CIM800 monitoring features include the fol-
lowing configurable items: 

Identifies all monitored contacts and signals to 
the Fire Controller, the status of monitored 
contacts and wiring to the contacts.

Can monitor a single normally closed contact.

Can monitor two Class B spur circuits, or a sin-
gle class Class A loop circuit.

When two Class B spur circuits are con-
nected, each must be of the same style. A 
monitored contact going to the active state, on 
either spur circuit, will cause the CIM800 to 
report the Active State back to the MX control-
ler.

An LED reports the CIM800 status to the user. 

The LED lights when the contact monitored by 
the CIM800 has switched to the active (off 
normal) state.

The LED when normally off, will pulse when 
the CIM800 is polled by the controller. 

Wiring notes

Mounting

Installation of modules into an ANC-
8 ancillary housing

The housing can accommodate up to eight ancil-
lary PCBs. A stacking kit is available if a second 
layer of PCBs is required.

How to install MX800 modules into an 
ANC-8 ancillary housing

1 Assemble the required ancillary PCBs onto the 

chassis plate as required, fixing as shown in Fig. 3.

2 Assemble the chassis plate into the housing and 

secure using fixing screw, see Fig. 2.

NOTICE

There are no user- circuit required set-
tings (such as switches or headers) on 
the CIM800.

All wiring must conform to the current 
edition of IEE Wiring Regulations and 
BS5839 part 1.

All conductors to be free of earths.

Fit the PCB to the M520 cover/ANC-8 
ancillary housing.

Connect wiring to the monitored con-
tact. For CIM800 typical wiring config-
urations (see Figures 6 to 11).

Verify the correct polarity of wiring 
before connecting the CIM800 to the 
addressable loop

Содержание CIM800

Страница 1: ...oring multi ple normally open contacts with short circuit giving a fault output Fig 1 CIM800 Contact Input Module Parameter Value Type Identification Value 145 System Compatibility Use only with MX Fire Alarm Control lers Environment Indoor Application only Operating Temperature 25 C to 70 C Storage Temperature 40 C to 80 C Operating Humidity Up to 95 non condensing Dimensions HWD 87 x 148 x 14 mm...

Страница 2: ...g to the active state on either spur circuit will cause the CIM800 to report the Active State back to the MX control ler An LED reports the CIM800 status to the user The LED lights when the contact monitored by the CIM800 has switched to the active off normal state The LED when normally off will pulse when the CIM800 is polled by the controller Wiring notes Mounting Installation of modules into an...

Страница 3: ...g must be applied Apply Loctite S1595 silicone sealant around the LED as shown in Fig 5 Note how the sealant fills the small gap between the LED and its hole in the cover Fig 2 ANC 8 Chassis Plate 1 Chassis plate fixing screw 2 Chassis plate 3 Cover earth 4 Chassis plate earth 5 Transit screw 6 Typical positions of 800 modules 4 per row CAUTION Ensure only nylon stand offs and washers are used 1 2...

Страница 4: ...the current issue of BS5839 Two pairs of con nection terminals L and L are provided on the terminal block These terminals are used for con necting the module onto the addressable circuit A maximum of one 1 5mm2 or one 2 5mm2 cable may be connected at any one terminal Associated equipment The module fits onto a standard dual gang MK box or an ANC8 ancillary housing Fig 5 Sealed LED 1 Cover 2 LED 3 ...

Страница 5: ...lly Closed Contacts Short Circuit A to A or B to B Fault 1 MX Controller 2 To next device 3 Programming port VE VE TB1 TB2 A A B B L L L L 100 200 100 200 1 2 3 NOTICE Ifonlyonecircuitisusedtheusercircuit must be terminated with 200 ohm EOL resistor MX CONSYS configuration selection style C normally open Mode 2 ...

Страница 6: ...ice 3 Programming port NOTICE MX CONSYS configuration selec tion style E normally closed Mode 6 VE VE TB1 TB2 A A B B L L L L 100 200 100 200 1 2 3 Fig 9 Loop Circuit Class A Normally Closed Contact Short Circuit A to A or B to B Fault 1 MX Controller 2 To next device 3 Programming port NOTICE MX CONSYS configuration selection style E normally open Mode 5 VE VE TB1 TB2 A A B B L L L L 100 200 1 2 ...

Страница 7: ... A A B B L L L L 100 200 1 2 3 NOTICE MX CONSYS configuration selection style B normally open Mode 1 If only one circuit is used the other cir cuitmustterminatedwithA200ohm EOL resistor Fig 11 Spur Circuit Class B Normally Open Contacts Short Circuit between A and A or B and B Alarm 1 MX Controller 2 To next device 3 Programming port VE VE TB1 TB2 A A B B L L L L 200 200 3 2 1 ...

Страница 8: ... configuration selection style D normally open Mode 4 Fig 12 Loop Circuit Class A Normally Open Contacts Short Circuit between A and A or B and B Alarm 1 MX Controller 2 To next device 3 Programming port VE VE TB1 TB2 A A B B L L L L 200 3 2 1 Name Stock code number CIM800 Contact Input Module 555 800 002 CIM800 Contact Input Module c w cover 555 800 032 M520 Double Gang Cover 517 035 007 ANC8 Anc...

Отзывы: