2/8
Installation Instructions Doc. version 4.0
MZX CIM800
MZX Fire detection system
Two spur circuits (Class B) monitoring single
normally closed contacts, with short circuit
giving a fault output.
Single loop circuit (Class A) monitoring a nor-
mally open contact, with short circuit giving a
fault output.
Single loop circuit (Class A) monitoring a nor-
mally closed contact, with short circuit giving
a fault output.
Two spur circuits (Class B) monitoring multi-
ple normally open contacts, with short circuit
giving an alarm.
Single loop circuit (Class A) monitoring multi-
ple normally open contacts, with short circuit
giving an alarm.
Features
The CIM800 monitoring features include the fol-
lowing configurable items:
Identifies all monitored contacts and signals to
the Fire Controller, the status of monitored
contacts and wiring to the contacts.
Can monitor a single normally closed contact.
Can monitor two Class B spur circuits, or a sin-
gle class Class A loop circuit.
When two Class B spur circuits are con-
nected, each must be of the same style. A
monitored contact going to the active state, on
either spur circuit, will cause the CIM800 to
report the Active State back to the MX control-
ler.
An LED reports the CIM800 status to the user.
The LED lights when the contact monitored by
the CIM800 has switched to the active (off
normal) state.
The LED when normally off, will pulse when
the CIM800 is polled by the controller.
Wiring notes
Mounting
Installation of modules into an ANC-
8 ancillary housing
The housing can accommodate up to eight ancil-
lary PCBs. A stacking kit is available if a second
layer of PCBs is required.
How to install MX800 modules into an
ANC-8 ancillary housing
1 Assemble the required ancillary PCBs onto the
chassis plate as required, fixing as shown in Fig. 3.
2 Assemble the chassis plate into the housing and
secure using fixing screw, see Fig. 2.
NOTICE
There are no user- circuit required set-
tings (such as switches or headers) on
the CIM800.
All wiring must conform to the current
edition of IEE Wiring Regulations and
BS5839 part 1.
All conductors to be free of earths.
Fit the PCB to the M520 cover/ANC-8
ancillary housing.
Connect wiring to the monitored con-
tact. For CIM800 typical wiring config-
urations (see Figures 6 to 11).
Verify the correct polarity of wiring
before connecting the CIM800 to the
addressable loop