Introduction
Chapter 1
OPERATION MANUAL
V2.3.0en/07.06.19//17.12
Unichiller®
15
1.3.1.1
Proper disposal of resources and consumables
Do comply with all national disposal regulations applicable for you. Contact your local waste man-
agement company for any questions concerning disposal.
Material / Aids
Disposal / Cleaning
Packing material
Keep the packaging material for future use (e.g. transport).
Thermal fluid
Please refer to the safety data sheet of the thermal fluid used for information on its
proper disposal.
Use the original thermal fluid container when disposing it.
Filling accessories, e.g.
beaker
Clean the filling accessories for reuse. Make sure that the materials and cleaning
agents used are properly disposed of.
Aids such as towels,
cleaning cloths
Tools used to take up spilled thermal fluid must be disposed of in the same fashion
as the thermal fluid itself.
Tools used for cleaning must be disposed of depending on the cleaning agent used.
Cleaning agents such as
stainless steel cleaning
agents, sensitive-fabrics
detergents
Please refer to the safety data sheet of the cleaning agent used for information on its
proper disposal.
Use the original containers when disposing of large quantities of cleaning agents.
Consumables such as air
filter mats, temperature
control hoses
Please refer to the safety data sheet of the consumables used for information on
their proper disposal.
1.3.1.2
Temperature control unit with natural refrigerants (NR)
Over 8 g refrigerant per m³ room air
DEATH OR SERIOUS INJURY DUE TO EXPLOSION
Observe the rating plate (amount of natural refrigerant contained) and the room size (maximum room
concentration of natural refrigerant in case of leakage) when installing the temperature control unit.
Over 8 g refrigerant per m³ room air: A gas warning sensor must be fitted and functioning.
The gas warning sensor must be calibrated and maintained at regular intervals (between 6 and
12 months).
The temperature control unit is not approved for operation
in an ATEX zone
.
Huber products with natural refrigerants work with numerous proven, safe and highly-sustainable
technologies. The relevant standards and regulations for temperature control units with natural
refrigerants contain a number of stipulations, the importance of complying with which is set out
below. Also observe on page 13 the section
.
Huber temperature control units are constructed to be permanently sealed and are carefully
checked for leak tightness. Temperature control units with more than 150 g natural refrigerant are
equipped with an additional gas warning sensor. To find out whether your temperature control unit
is equipped with a gas warning sensor, refer to the data sheet from page 85 in section
.
The fill quantity of your temperature control unit is stated on the data sheet (from page 85 in sec-
tion
) or on the rating plate on the rear of the temperature control unit. Observe page 25,
section
and page 27, section
.
Class of
application
field
Application field
Example of the installation
location
Max.
quantity of
refrigerant
AND
Max. permissible
quantity above
ground level (GL)
A
General
Publicly accessible area in a
public building
8 g/m
3
ambient air
1.5 kg
B
Monitored
Laboratories
2.5 kg
C
Access only for
authorized persons
Production equipment
10.0 kg
Temperature control units with
more than 1 kg
refrigerant
must not be installed below ground level
(GL).
Overview
Classifying the applica-
tion field
Содержание Unichiller 400T
Страница 1: ...Unichiller...
Страница 2: ......
Страница 3: ...OPERATION MANUAL Unichiller...
Страница 4: ......
Страница 6: ...OPERATION MANUAL Unichiller V2 3 0en 07 06 19 17 12 6 Pilot ONE Layout of the Home screen...
Страница 85: ...Annex Chapter 9 OPERATION MANUAL V2 3 0en 07 06 19 17 12 Unichiller 85 9 Annex...