UPS5000-S-600 kVA
User Manual (Three-phase, Three-wire)
8 Technical Specifications
Issue 05 (2019-12-20)
Copyright © Huawei Technologies Co., Ltd.
189
8
Technical Specifications
Table 8-1
Physical specifications
Item
Specifications
Cabling mode
Cables are routed from the top or bottom
Protection level
IP20 (IP21 can be reached by configuring IP21 components.)
Dimensions (H x W x
D)
2000 mm x 1400 mm x 850 mm
Communication
Supports dry contacts, RS485 ports, and FE ports. Supports
Simple Network Management Protocol (SNMP).
Weight
Net weight about 950 kg
Table 8-2
Environmental specifications
Item
Specifications
Operating temperature
0–40°C
Storage temperature
–40°C to +70°C
Relative humidity
0%–95% RH (non-condensing)
Altitude
0–1000 m
When the altitude is greater than 1000 m and less than 4000 m,
the rated power should be derated. For details, see the
IEC62040-3.
Table 8-3
Safety and EMC
Item
Specifications
Safety regulations
UL1778 (480 V)
EN62040-1: 2013