UPS5000-S-600 kVA
User Manual (Three-phase, Three-wire)
4 User Interface
Issue 05 (2019-12-20)
Copyright © Huawei Technologies Co., Ltd.
139
Item
Description
Default
Value
Value
Range
Bus Capa. Life
If this parameter is set to Enable, the UPS
detects the bus capacitor lifespan.
Disable
Disable,
Enable
Paral. sys.
hibernate
When customer loads are light, enable parallel
hibernation to alternate modules in hibernation
mode, which can prolong their service life and
improve the system efficiency.
Disable
Disable,
Enable
Hibernated
redundant
modules
Redundant modules required for hibernation.
1
0–19
Module cycle
hiber. period
(d)
Indicates the rotation interval of modules in
hibernation mode. The default value is 30,
which means that the hibernating module is
rotated every 30 days.
30
1–100
D.G. ECO
Bypass Supply
Indicates whether ECO bypass is allowed to
supply power in D.G. mode. When the D.G. is
connected to the dry contact signal GEN:
If this parameter is set to Enable, the system
can enter ECO bypass mode when the D.G.
supplies power to the bypass and the ECO
function is enabled.
If this parameter is set to Disable, the
system is not allowed to enter ECO mode
when the D.G. supplies power to the bypass.
Enable
Disable,
Enable
RAM
verification
Enable or disable the memory check function.
If this parameter is set to Enable, the control
chip RAM working status is checked regularly.
If this parameter is set to Disable, regular check
is disabled.
Disable
Disable,
Enable
Record time
after fault
Indicates the time for storing fault data after the
UPS experiences a fault. The default value is 0
ms, which means that the data during 20 ms
before the fault occurs is recorded. If the value
is set to 40 ms, it means that the data during 20
ms before the fault occurs and the data during
40 ms after the fault occurs are recorded, and
the like.
0 ms
0 ms, 20
ms, 40
ms, 60
ms, 80 ms
Collect
real-time site
waveform
If this parameter is set to Enable, one
waveform can be stored manually.
Disable
Disable,
Enable
Table 4-7
Input Setting
Item
Description
Default
Value
Value
Range