UPS5000-S-600 kVA
User Manual (Three-phase, Three-wire)
4 User Interface
Issue 05 (2019-12-20)
Copyright © Huawei Technologies Co., Ltd.
106
Figure 4-26
RS485 Settings
Item
Description
Default
Value
Value
Range
Address
This serial port address is allocated by the user.
1
1–254
Baud rate
Select a baud rate to match the user's network
management conditions onsite.
9600
9600,
19200,
115200
Parity mode
Verify the validity of RS485 communication
characters. When a device node adopts RS485
communication, ensure that the parity modes
for the device nodes are set to the same mode.
None
None,
Odd, Even
Stop bit
Stop bit in the Modbus communication frame
format. When the UPS is connected over the
serial port Modbus, set this parameter based on
the frame format that the upstream device
Modbus supports.
1
1, 2
On the
Comm Settings
screen, tap
ModbusTCP Settings
. The
ModbusTCP Settings
screen
is displayed.