UPS5000-S-600 kVA
User Manual (Three-phase, Three-wire)
4 User Interface
Issue 05 (2019-12-20)
Copyright © Huawei Technologies Co., Ltd.
115
Figure 4-37
Bypass Settings
Item
Description
Default Value
Value
Range
Maximum
bypass
voltage
When the difference between the
bypass voltage and the rated voltage
exceeds the upper threshold for the
bypass voltage, the system
determines that the bypass voltage is
not normal and that the bypass is
unavailable.
When the
voltage level is
380 V, the
default value is
+15%.
When the
voltage level is
400 V, the
default value is
+15%.
When the
voltage level is
415 V, the
default value is
+10%.
When the
voltage level is
420 V, the
default value is
+10%.
When the
voltage level is
480 V, the
default value is
+10%.
+10%,
+15%,
+20%,
+25%
Minimum
bypass
voltage
When the difference between the
bypass voltage and the rated voltage
exceeds the lower threshold for the
bypass voltage, the system
determines that the bypass voltage is
abnormal and that the bypass is
unavailable.
–20%
–10%,
–15%,
–20%,
–30%,
–40%