UPS5000-S-600 kVA
User Manual (Three-phase, Three-wire)
3 Installation
Issue 05 (2019-12-20)
Copyright © Huawei Technologies Co., Ltd.
51
Item
50 kVA
100
kVA
150
kVA
200
kVA
250
kVA
300
kVA
(kcmil/AWG)
L3
PE
8
4
4
3
2
1
Output
connector
Output current (A)
61
121
181
241
301
361
Recommended
cross-sectional
area
(kcmil/AWG)
U
3 x 4
3 x 2/0
3 x 4/0
3 x 350
2 x (3 x
3/0)
2 x (3 x
4/0)
V
W
PE
8
6
4
3
3
2
Battery
input
connector
Nominal battery
discharge current (A)
110
219
329
439
548
658
Maximum battery
discharge current (A)
131
263
394
525
657
788
Recommended
cross-sectional
area
(kcmil/AWG)
+
2 x 1/0
2 x 300
2 x (2 x
3/0)
2 x (2 x
300)
3 x (2 x
4/0)
3 x (2 x
300)
-
PE
6
4
3
1
1/0
1/0
Table 3-6
Recommended power cable cross-sectional area (350 kVA–600 kVA)
Item
350
kVA
400
kVA
450
kVA
500
kVA
550
kVA
600
kVA
Mains
input
connector
Mains input current (A)
488
558
627
697
767
836
Recommended
cross-sectional
area
(kcmil/AWG)
L1
2 x (3 x
350)
3 x (3 x
250)
3 x (3 x
300)
3 x (3 x
350)
3 x (3 x
400)
4 x (3 x
300)
L2
L3
PE
1/0
1/0
1/0
2/0
2/0
3/0
Bypass
input
connector
Bypass input current (A)
421
482
542
602
662
722
Recommended
cross-sectional
area
(kcmil/AWG)
L1
2 x (3 x
350)
3 x (3 x
250)
3 x (3 x
300)
3 x (3 x
350)
3 x (3 x
400)
4 x (3 x
300)
L2
L3
PE
1/0
1/0
1/0
2/0
2/0
3/0
Output
connector
Output current (A)
421
482
542
602
662
722
Recommended
cross-sectional
area
U
2 x (3 x
300)
2 x (3 x
350)
3 x (3 x
4/0)
3 x (3 x
250)
3 x (3 x
300)
3 x (3 x
350)
V