Figure 3-8 Installing a compute module
----End
3.4 Connecting External Cables
This topic describes how to connect external cables to the RH8100 V3.
3.4.1 Connecting a Ground Cable
Scenarios
●
When AC or high-voltage DC power supplies are used, the chassis is grounded
over the protective earth (PE) conductor of each power cable, and the chassis
ground terminal needs to be grounded as well. The server does not provide a
ground at delivery, so the customer needs to prepare a ground cable. The
cable model must be determined based on the site requirement.
●
When DC power supplies are used, the PSU ground terminal must be
grounded. The server does not provide a ground at delivery. The ground cable
model must be selected based on the site requirement.
The customer needs to prepare a UL 10 AWG yellow and green adhesive chassis ground
cable with a maximum length of 2 m. The ring tongue of the chassis ground terminal
requires M6 screws and must be configured based on the site requirements.
Prerequisites
Conditions
RH8100 V3 Server
User Guide
3 Installing the RH8100 V3
Issue 30 (2019-12-19)
Copyright © Huawei Technologies Co., Ltd.
89