Use temperature control devices regardless of climate or season.
●
In dry areas, mop the floor regularly or use a humidifier to increase humidity
in the equipment room.
●
In humid areas, use a dehumidifier to decrease humidity in the equipment
room.
Table 3-1 Temperature and humidity requirements
Item
Description
Temperature
5°C to 40°C (41°F to 104°F)
NOTE
When the 64 GB DIMMs or high-power GPUs
are configured, the maximum operating
temperature is 35°C (95°F).
Humidity
10% RH to 90% RH
Installation Rule
The RH8100 V3 is 8 U high and can be installed in a standard 19-inch cabinet.
Observe the following rule when installing the RH8100 V3:
●
Servers can be stacked in a cabinet. If the cabinet space is sufficient, the
distance between two adjacent servers is 1 U high.
●
The RH8100 V3 is heavy. Install it in the lower part of the cabinet to keep the
cabinet in balance.