A 2000 W AC PSU uses a C14 connector, which connects to a C13
connector on an AC power cable.
The rated voltage of the power cable must be at least 250 V, and the
cable current must be at least 10 A. The connector of the power
distribution unit (PDU) must be the same as the connector on the PSU.
–
A 3000 W AC PSU uses a C20 connector, which connects to a C19
connector on an AC power cable.
The rated voltage of the power cable must be at least 250 V, and the
cable current must be at least 16 A. The connector of the power
distribution unit (PDU) must be the same as the connector on the PSU.
●
If you use DC PSUs, a PGND cable is properly connected to the RH8100 V3.
Data
No data preparation is required for this operation.
Tools
ESD wrist strap or ESD gloves: used to prevent ESD damage
Procedure
Connect an AC power cable.
1. Connect one end of the AC power cable to the connector on an AC PSU of the
RH8100 V3. See step (1) in
RH8100 V3 Server
User Guide
3 Installing the RH8100 V3
Issue 30 (2019-12-19)