7
Alarm List
Table 7-1 General input unit alarm reference
Alarm ID
Alarm Name
Alarm
Severity
Possible Causes
Procedure
412177004 General input unit and
ECC800
communication failure
Critical
Communication with
the PoE module is
interrupted.
Check the cable
connection to the
general input unit.
412177000
-41217700
3
POE1/POE2/POE3/
POE4 output overload
Major
The output is
overloaded or the
power supply pin is
short-circuited.
● Check whether the
output is
overloaded.
● Check that the
power supply pin is
not short-circuited.
412177005 Detection board
abnormal
Critical
The monitoring board
hardware is faulty.
● Check that no
other alarm is
generated for the
monitoring board.
● Replace the
monitoring board.
412177006
-41217700
8
L1/L2/L3 open-phase
Critical
Phase voltage is
below the open-phase
threshold.
● Check the power
input.
● Use the power
supply with a
normal input
voltage.
New Main Way 2.0
User Manual
7 Alarm List
Issue 05 (2020-10-15)
Copyright © Huawei Technologies Co., Ltd.
51