Figure 3-9 Layout diagram
(1) General input unit (2) Power distribution
unit
(3) Aisle containment (4) Cross-row cable
tray
Figure 3-10 Cabling diagram
3.2.6 Layout and Cable Routing Principles: Dual-Row Aisle
Containment (N+1 Scenario)
●
The number of power distribution units on each NMW should be the same.
●
If the power density per cabinet is less than or equal to 10 kW, single-phase
power distribution units are used and each power distribution unit supports a
maximum of six IT or network cabinets. One power distribution unit provides
six power outputs to route A, and the other power distribution unit provides
six power outputs to route B for the corresponding cabinets.
●
If the power density per cabinet is greater than 10 kW, three-phase power
distribution units are used and each power distribution unit supports a
maximum of two IT or network cabinets. One power distribution unit provides
two power outputs to route A, and the other power distribution unit provides
two power outputs to route B for the corresponding cabinets.
●
The figures use the three-phase power distribution unit as an example.
New Main Way 2.0
User Manual
3 Installation
Issue 05 (2020-10-15)