Figure 2-2 Dual-route installation scenario
(1) General input unit (2) Connective kit
(3) Power distribution
unit
(4) Busbar trunking
unit
(5) Column
(6) Around-column
busbar trunking unit
and elbow (used in the
scenario with columns)
(7) End plug
(8) High support
2.1 General Input Unit
It is used as a cable entry unit.
Model Number Description
Figure 2-3 General input unit
No.
Meaning
1
New main way
2
Input MCCB current level:
0250: 250 A (derated to 187 A at 40°C)
0400: 400 A (derated to 300 A at 40°C)
3
AC
4
Rated 380–415 V, three-phase
5
General input unit
6
Monitoring type
7
01 right-mounted
02: left-mounted
New Main Way 2.0
User Manual
2 Overview
Issue 05 (2020-10-15)
Copyright © Huawei Technologies Co., Ltd.
7