Path
Parameter
Name
Default
Value
Setting
Upper load
current
threshold
80
When the load current
exceeds the preset
value, an alarm is
generated.
Lower load
current
threshold
60
When the load current
exceeds the preset
value, an alarm is
generated.
2. Set the parameters for other general input units in the same way or by
synchronizing parameters.
Path: Maintenance > Parameter Sync
Step 2 Set parameters for power distribution units on the ECC800-Pro WebUI.
1. (Optional) To modify the branch signal name of the power distribution unit,
choose System Settings > Signal Name Modify and access the Batch Signal
Configuration to modify the name, and then tap Submit.
2. The following is an example of how to display two branches for power
distribution unit 1.
Choose Monitoring > Power Distribution > General Input Unit > Power
Distribution Unit > Display Configuration, select Branch Information
Display corresponding to QF1 and QF2, and then tap Submit.
3. Configure the power distribution settings for power distribution unit 1.
Table 4-2 Power distribution settings for a power distribution unit
Path
Parameter Name
Defaul
t Value
Description
Monitoring >
Power
Distribution
> General
Input Unit1
> Power
Distribution
Unit >
Running
Parameters >
Unhide All
Advanced
Signals >
Power
Distribution
Settings
QF1 Rated current (L1)
(This parameter is not
displayed for some
distribution units.)
QF2 Rated current (L2)
(This parameter is not
displayed for some
distribution units.)
32
Rated current 32 A
for each branch.
New Main Way 2.0
User Manual
4 Power-On Commissioning
Issue 05 (2020-10-15)
Copyright © Huawei Technologies Co., Ltd.
46