IDS1000 Container Data Center
User Manual
4 Routine Maintenance
Issue 01 (2014-3-15)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
31
Maintena
nce Item
Operation
Expected Result
Troubleshooting
vessel are installed
securely.
All nozzle openings
are not blocked.
Gas
pressure of
the fire
cylinder
Observe the
pointer on the
barometer of
the fire
cylinder.
The pointer is in the
green area.
If the pointer is not in the
green area, contact Huawei
technical support.
4.5 Quarterly Maintenance
Maintena
nce Item
Operation
Expected
Result
Troubleshooting
Alarm
indicator on
smoke
detectors
Observe the
alarm indicator
on each smoke
detector.
The alarm
indicator blinks
once every six
seconds.
If an alarm indicator blinks twice
every six seconds or does not blink,
the smoke detector is faulty or the
cables are not properly connected.
Connect the cables or replace the
smoke detector. For details, see the
operations described in
Alarm
indicator on
heat
detectors
Observe the
alarm indicator
on each heat
detector.
The alarm
indicator blinks
once every six
seconds.
If an alarm indicator blinks twice
every six seconds or does not blink,
the heat detector is faulty or the cable
is not properly connected. Connect
the cables or replace the heat
detector. For details, see the
operations described in
Audible and
visual alarm
Trigger a
smoke detector
and a heat
detector.
Audible and
visual alarms are
generated.
If no alarm is generated, the audible
and visual alarm is faulty or the cable
is not properly connected. Rectify the
fault by following the instructions in
6.4 Audible and Visual Alarm Fault
Fire alarm
bell
Trigger a
smoke detector
or a heat
detector.
The fire alarm
bell rings.
If the fire alarm bell does not ring,
the alarm bell is faulty or the cable is
not properly connected. Connect the
cable or replace the alarm bell. For
details, see the operations described
in