IDS1000 Container Data Center
User Manual
3 Power-On Commissioning
Issue 01 (2014-3-15)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
16
Figure 3-6
Setting the power-on delay for the solenoid valve from 25s to 30s
The factory setting for the solenoid valve power-on delay is 30s, as shown in
Figure 3-7
Setting the initial power-on delay for the solenoid valve
Step 5
Set the gas extinguishing controller time display.
Open the controller panel and calibrate time from the rear of the display panel.
There are three buttons and one light emitting diode on the rear of the panel. The three buttons are
Switchover S12
,
Former plus S11
, and
Later plus S10
, respectively, which are used to calibrate time.
Former plus
means plus 1 for the first two values of the nixie tube, and
Later plus
means
plus 1 for the last two values of the nixie tube. The adjustment methods are as follows:
1.
Press
Switchover S12
, and the H11 indicator lights up, indicating that the time is being
calibrated. The nixie tube displays the year in the format of
??
. Press
Later plus S10
to
add the value, which ranges from 1 to 60.
2.
Then press
Switchover S12
, and the nixie tube displays the month and day in the format
of
??.??
.
Press
Former plus S11
to adjust the month, which ranges from 1 to 12, and then press
Later plus S10
to adjust the date, which ranges from 1 to 31.
3.
Press
Switchover S12
again to display hour and minute, which is in the format of
??:??
.
Press
Former plus S11
to adjust the month, which ranges from 1 to 23. Then press
Later plus S10
to adjust the day, which ranges from 0 to 59.
4.
Press
Switchover S12
again to finish the time setting. The indicator H11 lights off. The
nixie tube displays the hour and minute.