IDS1000 Container Data Center
User Manual
1 Configuration Description
Issue 01 (2014-3-15)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
3
Compone
nt Name
Appearance
Function
Atomizer
nozzle
Sprays an extinguishing agent to aisles in case
of a fire.
Gas release
indicator
Displays "DON'T ENTER WHILE
RELEASING GAS" to warn onsite personnel
in case of a fire and the fire extinguishing
equipment releases the extinguishing agent into
the protected zone.
Audible and
visual alarm
Generates dazzling flash signals and shrill
audible signals in case of a fire, reminding
onsite personnel to evacuate from the site
immediately, thereby avoiding major accident.
Emergency
start/abort
switch
Starts or stops the gas extinguishing equipment
in case of a fire. The device is installed outside
the door of the protected zone. If you press the
glass plate to start extinguishing in emergency,
the red indicator lights up.
Heat
detector
Evenly deployed in the aisles inside containers
to detect the temperature inside the containers
in real time. When it works in monitoring
mode, the red indicator blinks. When the
ambient temperature exceeds the alarm
threshold, it enters alarm mode and the red
indicator is steady on.
Smoke
detector
Evenly deployed in the aisles inside containers
to detect the smoke density inside the
containers in real time. When it works in
monitoring mode, the red indicator blinks.
When the onsite smoke density exceeds the
alarm threshold, it enters alarm mode and the
red indicator is steady on.
Alarm bell
Produces clear and consistent sounds in case of
a fire, reminding onsite personnel to evacuate
from the site immediately, thereby avoiding
major accident.
System Features
All surface-mounted fire control cables are routed through metal hoses. The hose ends
are protected with grommets to prevent damage in case of a fire. Fire control cables are
routed and used separately which ensures secure and reliable power supplies to the fire
extinguishing system.