FusionModule1000A20 CT Solution
Maintenance Guide
5 Parts Replacement
Issue 01 (2019-02-25)
Copyright © Huawei Technologies Co., Ltd.
76
Procedure
Step 1
Switch off the power circuit breaker of the hydrogen collector.
Step 2
Open the cable trough, and cut off the power cable to the hydrogen exhaust fan using a cable
cutter.
Reserve a segment of the power cable at the quick-connect terminal when cutting the power cable to the
hydrogen exhaust fan.
Step 3
Bind the reserved segment of the power cable for the hydrogen exhaust fan to the main line
using insulation tape to avoid dangers.
Step 4
Remove the cover of the hydrogen exhaust fan using a Phillips screwdriver.
Step 5
Remove the screws securing the hydrogen exhaust fan using a Phillips screwdriver.
Figure 5-8
Removing the cover
Step 6
Install the spare hydrogen exhaust fan, and tighten it using a Phillips screwdriver.
Figure 5-9
Installing the hydrogen exhaust fan