FusionModule1000A20 CT Solution
Maintenance Guide
5 Parts Replacement
Issue 01 (2019-02-25)
Copyright © Huawei Technologies Co., Ltd.
88
5.3.9 Replacing a Water Sensor (Point Type)
Prerequisites
Spare water sensors of the same model are available and functional.
Impact on the System
None
Preparations
Tools: Phillips screwdriver, protective gloves
Material: spare water temperature sensor
Documents: monitoring device layout, management system initial configuration table
Skill requirement: weak-current engineer
For the diagrams and tables, see the initial configuration parameter manual for the solution in use.
Procedure
Step 1
Locate the water sensor to be replaced based on the alarm information on the monitoring
software terminal. Figure 5-18 shows a point-type water sensor.
Figure 5-18
Point-type water sensor
Step 2
Remove the locking bolts of the water sensor using a Phillips screwdriver, and remove the
water sensor, as shown in Figure 5-19.