FusionModule1000A20 CT Solution
Maintenance Guide
3 Routine Maintenance
Issue 01 (2019-02-25)
Copyright © Huawei Technologies Co., Ltd.
24
Check
Item
Operation
Check Standard
Troubleshooting
RF_Z
indicator
On: No network
parameters exist. A
network is waiting
to be created.
Blinking slowly: A
network is set up,
and node access is
not allowed (the
indicator blinks at
0.5 Hz, on for 1s
and then off for 1s).
Blinking at super
short intervals: A
network is set up,
and node access is
allowed (the
indicator blinks at
10 Hz, on for 0.05s
and then off for
0.05s).
Blinking at super
short intervals
intermittently: The
device is searching
for a network (the
indicator blinks at 2
Hz, on for 0.5 and
then off for 0.5s).
Refer to
ECC800 Data Center
Controller V100R001C30 User
Manual
to register the device, or
contact Huawei technical support.
Table 3-6
Monthly maintenance checklist for the monitoring system
Check
Item
Operation
Check Standard
Troubleshooting
AC
actuator
Power input
Input voltage:
90–240 V AC
Check the input power cables if the
input voltage is abnormal.
Power output
Output voltage:
90–240 V AC
For details, contact Huawei technical
support.
PWR
indicator
Steady on: The
power supply is
normal.
Off: No power
supply is available.
Check the input power cables.